Chapter 6 – Preventive Maintenance
Method 2 A
6-4
Capacitor reforming is realised by connecting a rectifier and a resistor
circuit to the converter DC link. The reforming circuit and component
values for different voltages are given below. See Figure 6-1 for the
reforming time.
WARNING! The converter supply must be disconnected while the
reforming circuit is connected.
Disconnect
1.35 ×U
1
Supply Voltage
380 V < U
380 V < U
525 V < U
U
1
A
C
L–
A
< 415 V
SKD 82/16
1
< 500 V
SKD 82/16
1
< 690 V
SKD 82/16
1
or phase module
R
L+
Converter
Recommended Components
R
220 Ohm / 700 W
22 nF / 2000 V
470 Ohm / 1200 W
22 nF / 2000 V
680 Ohm / 1700 W
22 nF / 2000 V
ACS 600 MultiDrive
W2 (W1)
V2 (V1)
U2 (U1)
C