Power Cable Specifications - Huawei PDU8000-0630ACV4-SCA108 User Manual

Precision pdc-t
Table of Contents

Advertisement

PDU8000 Precision PDC-T
User Manual
No.
4
5
6
7
8
9

2.3.2 Power Cable Specifications

YJV 5-core cables are recommended. When the ambient temperature is 40° C, the conductor
working temperature cannot exceed 90° C.
Table 2-6 Power cable specifications
Wiring
Terminal
Power input
(L/N)
Power input
(PE)
AC output
(L)
Issue 01 (2017-07-15)
Cable Layout Rule
Cables are neatly arranged, and cable insulation layers are intact.
Different types of cables are bound separately.
Connection ports and cabling methods facilitate maintenance, cable
routing, and capacity expansion.
Cable connectors prepared onsite must be normal, secure, reliable, and
neat.
Power cables, ground cables, and various signal cables are securely
connected. Adapters are securely plugged or screwed.
The N and PE cables are bound separately from the L1/L2/L3 or L cables
for each circuit breaker. Cables are converged at the beam and bound in
groups by cable ties.
Rated
Recommende
Current (A)
d
Cross-Section
al Area (mm
160
50
250
95
400
185
630
2 x 185
160
25
250
50
400
95
630
2 x 95
< 10
2.5
10 ≤ I ≤ 40
6
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Terminal/Bolt
Specifications
)
2
DT-M10
DT-M12
DT-M16
DT-M16
DT-M10
DT-M10
DT-M12
DT-M12
Cord end
terminal (plug
depth 8-12 mm)
Cord end
terminal (plug
depth 8-12 mm)
2 Installation Guide
Recommended
Torque (N· m)
27
47
120
120
27
27
47
47
1.6
1.6
12

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pdu8000 series

Table of Contents