Connection Examples And Program Sequence; Doubling The Safety Time With Direct Spark Flame Burners; Burner Without Air Damper; Reversed Polarity Protection With Agm30 - Siemens LFL1.133 Manual

Burner controls
Table of Contents

Advertisement

Connection examples and program sequence

Doubling the safety time with direct
spark flame burners

Burner without air damper

Reversed polarity protection with
AGM30
2-stage direct spark flame burner
L...
16
17 18
LR
11
SA
IV
13
12
BV1
BV2
Z
N
A
T P
R
t7
t1
M1
M
~
M2
t3
Z
BV1
R
LR
100%
M
min.
LK
0...
BV2
t12
t11
FS
Building Technologies Division
16
17 18
19
Z
BV1
N
7451a10/1295
Extension of the safety time is only permitted if in compliance with the
relevant national standards.
11 10 8
6
M
N
AGM30
1
LR
SA
BV1/BV2
19
9 20 11
10
8
7
1
6 5 2 10 8
II
I
III
M
N
3
4
9
LK
7451a03/0396
C
B
t6
TSA
t4 t5
t13
7451a06/0600
Only with burner controls of the 01
BV2
series.
This circuit change (linking terminals
17 and 18) reduces the preignition
time by 50 %.
If the case of burners with no air
damper (or with an air damper not
controlled and monitored by the
burner control), terminals 8 and 6
7451a11/0396
must be linked, as otherwise the
burner control will not be able to start
the burner.
If the mains cables (L-N) are
switched, the AGM30 simulates a
flame signal (extraneous light). The
burner initiates lockout.
23
Load control by a 2-position controller. The air damper is
closed during burner off periods.
D
Control of actuator «SA» according to the single-wire
principle (actuator «SA»: E.g. SQN3... according to Data
Sheet N7808). For other connections, refer to
«Connection diagrams».
21/25
CC1N7451en
20.11.2017