Sizing; Derating; Cooling Air Flow Requirements - ABB ACS350 User Manual

Drives with ip66 casing (0.37 7.5 kw, 0.5 10 hp)
Hide thumbs Also See for ACS350:
Table of Contents

Advertisement

Sizing

The current ratings are the same regardless of the supply voltage within one voltage range. To achieve
the rated motor power given in the table, the rated current of the drive must be higher than or equal to
the rated motor current.
Note 1: The maximum allowed motor shaft power is limited to 1.5 · P
torque and current are automatically restricted. The function protects the input bridge of the drive
against overload.
Note 2: The ratings apply at ambient temperature of 40°C (104°F).

Derating

The load capacity decreases if the installation site ambient temperature exceeds 40°C (104°F) or if the
altitude exceeds 1000 meters (3300 ft). Derating is not allowed.

Cooling air flow requirements

The table below specifies the heat dissipation in the main circuit at nominal load and
in the control circuit with minimum load (I/O and panel not in use) and maximum load
(all digital inputs in the on state and the panel, fieldbus and fan in use). The total heat
dissipation is the sum of the heat dissipation in the main and control circuits.
Type
ACS350-
x = E/U
Rated I
3-phase U
= 200...240 V (200, 208, 220, 230, 240 V)
N
03x-02A4-2
03x-03A5-2
03x-04A7-2
03x-06A7-2
03x-07A5-2
03x-09A8-2
03x-13A3-2
112
03x-17A6-2
152
3-phase U
= 380...480 V (380, 400, 415, 440, 460, 480 V)
N
03x-01A2-4
03x-01A9-4
03x-02A4-4
03x-03A3-4
03x-04A1-4
03x-05A6-4
03x-07A3-4
03x-08A8-4
03x-12A5-4
130
03x-15A6-4
173
Heat dissipation
Main circuit
and I
1N
2N
W
BTU/Hr
W
19
65
6.1
31
106
6.1
38
130
9.5
60
205
9.5
62
212
9.5
83
283
10.5
383
10.5
519
10.5
11
38
6.6
16
55
6.6
21
72
9.8
31
106
9.8
40
137
9.8
61
208
9.8
74
253
14.1
94
321
14.1
444
12.0
591
12.0
. If the limit is exceeded, motor
N
Control circuit
Min
Max
BTU/Hr
W
BTU/Hr
21
22.7
21
22.7
32
26.4
32
26.4
32
26.4
36
27.5
36
27.5
36
27.5
23
24.4
23
24.4
33
28.7
33
28.7
33
28.7
33
28.7
48
32.7
48
32.7
41
31.2
41
31.2
Air flow
3
3
m
/h
ft
/min
78
-
-
78
-
-
90
-
-
90
-
-
90
-
-
94
-
-
94
-
-
94
-
-
83
-
-
83
-
-
98
-
-
98
-
-
98
-
-
98
-
-
112
-
-
112
-
-
107
-
-
107
-
-
00353783.xls G
Technical data
39

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs350 series

Table of Contents