ABB TTH200 Commissioning Instruction

Head mounted temperature transmitter
Hide thumbs Also See for TTH200:

Advertisement

CI/TTH200-EN
TTH200
Commissioning Instruction
Head mounted Temperature Transmitter
TTH200

Advertisement

Table of Contents
loading

Summary of Contents for ABB TTH200

  • Page 1 CI/TTH200-EN TTH200 Commissioning Instruction Head mounted Temperature Transmitter TTH200...
  • Page 2 Tel.: +49 551 905-534 Fax: +49 551 905-555 CCC-support.deapr@de.abb.com © Copyright 2009 by ABB Automation Products GmbH Subject to changes without notice This document is protected by copyright. It assists the user in safe and efficient operation of the device.
  • Page 3: Table Of Contents

    Zone 0 ..............................17 4.6.3 Zone 1 (0)..............................17 4.6.4 Zone 1 (20)............................18 4.6.5 Zone 2 ..............................18 Ex relevant specifications ..........................19 TTH200-E1, Intrinsic Safety ATEX.......................19 TTH200-H1, Intrinsic Safety IECEx......................19 Safety specifications for Intrinsic Safety ATEX / IECEx................19 2 - EN TTH200 CI/TTH200-EN...
  • Page 4 Contents TTH200-E2, Non-Sparking ATEX ........................19 TTH200-L1, Intrinsically Safe FM.........................19 TTH200-L2, Non-Incendive FM........................19 TTH200-R1, Intrinsically Safe CSA......................19 TTH200-R2, Non-Incendive CSA.........................19 HMI LCD display type AS..........................20 Ex relevant specifications..........................20 6.1.1 Intrinsic Safety ATEX ..........................20 6.1.2 Intrinsic Safety IECEx ...........................20 6.1.3 Safety specifications for Intrinsic Safety ATEX / IECEx................20 6.1.4...
  • Page 5: Safety

    (see the "Specifications" chapter in the operating instructions or on the data sheet). • The maximum operating temperature must not be exceeded. • The permitted operating temperature must not be exceeded. • The housing protection type must be observed. 4 - EN TTH200 CI/TTH200-EN...
  • Page 6: Target Groups And Qualifications

    Prior to using corrosive and abrasive materials for measurement purposes, the operator must check the level of resistance of all parts coming into contact with the materials to be measured. ABB Automation Products GmbH will gladly support you in selecting the materials, but cannot accept any liability in doing so.
  • Page 7: Plates And Symbols

    Failure to observe this safety information may result in damage to or destruction of the product and/or other system components. IMPORTANT (NOTICE) This symbol indicates operator tips, particularly useful information, or important information about the product or its further uses. It does not indicate a dangerous or damaging situation. 6 - EN TTH200 CI/TTH200-EN...
  • Page 8: Name Plate

    The name plate is located on the transmitter housing. TTH200 Automation Products GmbH Alzenau Germany 2008 ® HART O-Code: TTH200-E1H 00001234560000 Ser.-No: 123456789012 HW. Rev. 1.06 U = +11...30 V, I = 4...20 mA, HART SW. Rev. 01.00.02 Cfg: 1 x Pt100 3W; 0...100°C...
  • Page 9: Transport Safety Information

    Specifications” chapter and in the data sheet are complied with and that the power supply voltage corresponds with the voltage of the transmitter. When there is a chance that safe operation is no longer possible, put the device out of operation and secure against unintended operation. 8 - EN TTH200 CI/TTH200-EN...
  • Page 10: Use In Potentially Explosive Atmospheres

    Housing degree of protection The connection parts of the TTH200-E1H temperature transmitter and the HMI type AS LCD display must be installed so that a housing degree of protection type of at least IP 20 as per IEC 60529:1989 is achieved.
  • Page 11: Mounting

    1. Release the screw plug (3) for the cover of the connection head. 2. Open the cover (1). 3. Secure the transmitter (2) at the proper position on the cover, using the captive screws found in the transmitter. 10 - EN TTH200 CI/TTH200-EN...
  • Page 12: Installation On The Measuring Inset

    6. Place the transmitter in the housing on the measuring inset and secure it. Important The toothed discs between measuring inset and transmitter are straightened when the screws are tightened. This enables them to grip the mounting screws. CI/TTH200-EN TTH200 EN - 11...
  • Page 13: Installation On A Top Hat Rail

    Installing/Removing the optional LCD display A00087 Fig. 5: HMI type AS LCD display Thanks to the LCD display interface, the TTH200 can be operated freely with the HMI type AS LCD-display, enabling process data to be visualized. Important The LCD display with HMI type A configuration function, used with the TTx300 series, is not suitable for the TTH200.
  • Page 14: Electrical Connection

    Important The signal cable wires must be provided with wire end sleeves. The slotted screws of the connection terminals are tightened with a size 1 screwdriver (3.5 or 4 mm). CI/TTH200-EN TTH200 EN - 13...
  • Page 15: Conductor Material

    For the solder terminal, a soldering tag is provided at each terminal. A00237 Fig. 7 Potentiometer, Four-wire circuit RTD, Four-wire circuit Voltage measurement Potentiometer, Three-wire circuit RTD, Three-wire circuit Thermocouple Potentiometer, Two-wire circuit RTD, Two-wire circuit 14 - EN TTH200 CI/TTH200-EN...
  • Page 16: Standard Application

    + 0.02 A x (R Mmin Smin Where: Minimum operating voltage of transmitter Mmin Minimum supply voltage of repeater supply isolator / PLC input Smin Line resistance between transmitter and supply isolator Resistance for HART functionality CI/TTH200-EN TTH200 EN - 15...
  • Page 17: Electrical Interconnection In Explosion Hazardous Areas

    Transmitters can be installed in all kinds of industrial sectors. Explosion hazardous areas are divided into zones, meaning that a wide range of different instruments are also required. The Ex relevant specifications are stipulated in the section titled " Ex relevant specifications ". 16 - EN TTH200 CI/TTH200-EN...
  • Page 18: Zone 0

    The input for the supply isolator must have an [Ex ib] design. The user must ensure that sensor instrumentation meets the requirements of applicable Ex standards. It can be installed in Zone 1 or Zone 0. CI/TTH200-EN TTH200 EN - 17...
  • Page 19: Zone 1 (20)

    For instruments in Zone 2, the transmitter must be installed in a suitable housing with a degree of protection of at least IP 54. In the event of a disturbance, it must be ensured that the supply voltage cannot exceed the normal voltage by more than 40 %. 18 - EN TTH200 CI/TTH200-EN...
  • Page 20: Ex Relevant Specifications

    Change from one to two columns TTH200-E2, Non-Sparking ATEX TTH200-E1, Intrinsic Safety ATEX Explosion protection Explosion protection The TTH200 complies with the requirements of The TTH200 complies with the requirements of ATEX directive 94/9/EC ATEX directive 94/9/EC Approved for use in Zone 2.
  • Page 21: Hmi Lcd Display Type As

    Protection type intrinsic safety Ex ia IIC Supply circuit Max. voltage = 9 V Short circuit current = 65.2 mA Max. power = 101 W Internal inductance = 0 mH Internal = 0 nF capacitance Change from one to two columns 20 - EN TTH200 CI/TTH200-EN...
  • Page 22: Appendix

    Identification for intended use in potentially explosive atmospheres according Protection ATEX directive IEC standards FM Approvals (US) CSA International (Canada) Important All documentation, declarations of conformity, and certificates are available in ABB's download area. www.abb.com/temperature CI/TTH200-EN TTH200 EN - 21...
  • Page 23 Appendix 22 - EN TTH200 CI/TTH200-EN...
  • Page 24 ABB has Sales & Customer Support expertise in The Company’s policy is one of continuous product over 100 countries worldwide. improvement and the right is reserved to modify the information contained herein without notice. www.abb.com/temperature Printed in the Fed. Rep. of Germany (03.2009) ©...