Page 4
Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2014/30/EU) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2014/35/EU). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Page 9
Table of contents Indication bits mirrored in registers........40 SSR1 System status register (1) device health......40 SSR2 System status register (2) protection relay's mode and state.................41 SSR3 System status register (3) data available 1 (client- dependent)................41 SSR4 System status register (4) data available 2 (client- dependent, user-definable)............
Section 1 1MRS757464 C Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the protection relay. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a...
ABB Web site http://www.abb.com/relion. 1.3.2 Document revision history Document revision/date Product version History A/2011-11-18 First release B/2016-02-22 Content updated to correspond to the product version C/2019-04-10 Content updated Download the latest documents from the ABB Web site http://www.abb.com/substationautomation. REM611 Point List Manual...
Section 1 1MRS757464 C Introduction 1.3.3 Related documentation Name of the document Document ID Modbus Communication Protocol Manual 1MRS757461 Symbols and conventions 1.4.1 Symbols The caution icon indicates important information or warning related to the concept discussed in the text. It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property.
Section 1 1MRS757464 C Introduction The corresponding parameter values are "On" and "Off". • Input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE. • This document assumes that the parameter setting visibility is "Advanced". 1.4.3 Functions, codes and symbols Table 1:...
Section 2 1MRS757464 C Modbus data mappings Section 2 Modbus data mappings Overview This document describes the Modbus data points and structures available in the IED. The point list describes a superset of all data available through the standard configuration/s including the optional functionalities. The majority of the Modbus data points are valid for all standard configurations.
Section 2 1MRS757464 C Modbus data mappings Function IEC 61850 ME/C101 Runtime counter for machines and devices MDSOPT Logging Disturbance recorder RDRE Fault recorder FLTRFRC Measurement Three-phase current measurement CMMXU Sequence current measurement CSMSQI Residual current measurement RESCMMXU Other Input switch group ISWGAPC Output switch group OSWGAPC...
Section 2 1MRS757464 C Modbus data mappings 2.3.1 Premapped indications 2.3.1.1 Common data 1 Table 4: Common data 1 BitA RegA IEC 61850 name SA name Description Values CTRL.LLN0 2720 170.00 .Loc.stVal Remote/Local state 0/1=Rem/Loc 2721 170.01 .LocKeyHMI.stVal.Statio Station state 1=Station DR.RDRE1 2722...
Section 2 1MRS757464 C Modbus data mappings 2.3.1.12 LD0.LEDGGIO1 Indication LED states Color1/Color2 These LED indication points interpret the case when a signal is wired to both the OK and ALARM inputs, but inverted to the other. This means that the LED toggles between red and green colors.
Section 2 1MRS757464 C Modbus data mappings BitA RegA IEC 61850 name SA name Description Values 3529 220.09 .LEDSt10.stVal LED 10 state 0/1=Color1/2 3530 220.10 .LEDSt11.stVal LED 11 state 0/1=Color1/2 3531 220.11 <reserved> 1) Check Communication Management tool in PCM600 or LHMI or WHMI to confirm the availability for a particular device configuration. 2.3.1.13 LD0.LEDGGIO1 Indication LED states OFF/ColorX These LED indication points interpret the case when an indication signal is wired to...
Section 2 1MRS757464 C Modbus data mappings BitA RegA IEC 61850 name SA name Description Values 2777 173.09 .LEDSt10.stVal LED 10 state 0/1=Off/Color 2778 173.10 .LEDSt11.stVal LED 11 state 0/1=Off/Color 2779 173.11 <reserved> 1) Check Communication Management tool in PCM600 or LHMI or WHMI to confirm the availability for a particular device configuration. 2.3.1.14 LD0.LEDPTRC1 Global conditioning (1) Table 17:...
Section 2 1MRS757464 C Modbus data mappings 2.3.1.16 LD0.LOFLPTUC1 Loss of load supervision (1) Table 19: LD0.LOFLPTUC1 Loss of load supervision (1) BitA RegA IEC 61850 name SA name Description Values LD0.LOFLPTUC1 2912 182.00 .Str.general START Stage start 1=Start 2913 182.01 .mcd 2914...
Section 2 1MRS757464 C Modbus data mappings 2.3.2 Unmapped indications Unmapped indications are indication data that have no initial Modbus mapping locations, but can be added to the user-definable Modbus area using the Communication Management tool in PCM600. If Modbus events are enabled for these indication signals, the event identification is the user-definable area address.
Section 2 1MRS757464 C Modbus data mappings BitA RegA IEC 61850 name SA name Description Values LD0.GNRLLTMS1 .TmChSt1.stVal Time synch. status 0/1=Down/Up .mcd .TmSyn.stVal IEC 61850-9-2 sync 0...2 .mcd .TmSrcSt.stVal Time sync source 0...99 .mcd LD0.SCHLCCH1 .ChLiv.stVal CH1LIV Ethernet channel 1 live 1=Live .mcd LD0.SCHLCCH2...
Section 2 1MRS757464 C Modbus data mappings Column name Description IEC 61850 Original IED data object identification. Described in the IEC 61850 format as Logical name Device.Logical Node and thereafter .Data Object.Data Attribute. Logical Node is the same as the application function block name. SA name The signal may have a defined label that is visible, for example, in the Application Configuration tool in PCM600.
Section 2 1MRS757464 C Modbus data mappings 2.4.1.4 Control structure 3 Table 46: Control structure 3 RegA Type Scale IEC 61850 name SA name Description Values 8011 Execute register 8012 Password reg 1 acc to setting 8013 Password reg 2 acc to setting 8014 Control register...
Section 2 1MRS757464 C Modbus data mappings 2.4.1.8 Control structure 7 Table 50: Control structure 7 RegA Type Scale IEC 61850 name SA name Description Values 8031 Execute register 8032 Password reg 1 acc to setting 8033 Password reg 2 acc to setting 8034 Control register...
Page 37
Section 2 1MRS757464 C Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values Timestamp of record 9254 - Year, Month Year/Month 9255 - Day, Hour Day/Hour 9256 - Minute, Second Min/Sec 9257 - Millisecond Millisecond 9258 Event identification 9259 Data object ID1...
Page 38
Section 2 1MRS757464 C Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values Record 4 data to read: If selected 9285 - Record sequence num 1...500 9286 - Unread records left 0...499 Timestamp of record 9287 - Year, Month Year/Month 9288...
Page 39
Section 2 1MRS757464 C Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values 9315 Data object ID2 9316 Event data value 1 9317 Event data value 2 Record 7 data to read: If selected 9318 - Record sequence num 1...500 9319 - Unread records left...
Section 2 1MRS757464 C Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values 9343 - Day, Hour Day/Hour 9344 - Minute, Second Min/Sec 9345 - Millisecond Millisecond 9346 Event identification 9347 Data object ID1 9348 Data object ID2 9349 Event data value 1 9350...
Section 2 1MRS757464 C Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values 9406 Minute, second Min/Sec 9407 Millisecond Millisecond 9408 Timestamp quality 2.4.1.13 Fault record data The table shows all potential data available in the fault record application. Which data is actually recorded depends on the functions available and enabled in the IED configuration.
Page 42
Section 2 1MRS757464 C Modbus data mappings RegA Type Scale SA name Description Values IEC 61850 name 9428 1000 .DifAPhsA.mag.f Diff. current phs A 0.000...80.00 0 [pu] 9429 1000 .DifAPhsB.mag.f Diff. current phs B 0.000...80.00 0 [pu] 9430 1000 .DifAPhsC.mag.f Diff.
Page 43
Section 2 1MRS757464 C Modbus data mappings RegA Type Scale SA name Description Values IEC 61850 name 9452 1000 .PPVPhsCA1.mag.f Voltage phs CA(1) 0.000...4.000 [×Un] 9453 1000 .VRes1.mag.f Voltage Uo(1) 0.000...4.000 [×Un] 9454 1000 .VZro1.mag.f Voltage Zro-Seq(1) 0.000...4.000 [×Un] 9455 1000 .VPsSeq1.mag.f Voltage Ps-Seq(1)
Page 44
Section 2 1MRS757464 C Modbus data mappings RegA Type Scale SA name Description Values IEC 61850 name 9477 1000 .ANgSeq2.mag.f Current Ng-Seq(2) 0.000… 50.000 [×In] 9478 1000 .PhVPhsA2.mag.f Voltage phs A(2) 0.000...4.000 [×Un] 9479 1000 .PhVPhsB2.mag.f Voltage phs B(2) 0.000...4.000 [×Un] 9480 1000...
Section 2 1MRS757464 C Modbus data mappings RegA Type Scale SA name Description Values IEC 61850 name 9501 1000 .APhsB3.mag.f Phase B current (c) 0...50.000 [×In] 9502 1000 .APhsC3.mag.f Phase C current (c) 0...50.000 [×In] 9503 1000 .ARes3.mag.f Residual current (c) 0...50.000 [×In] 9504...
Section 2 1MRS757464 C Modbus data mappings 2.4.1.16 Indication bits mirrored in registers The pre-mapped indication bit data has been mapped from indication bit address 2720 onwards. The bit data is mirrored in registers starting from register address 170 onwards. Table 58: Indication bits mirrored in registers RegA...
Section 2 1MRS757464 C Modbus data mappings 2.4.1.18 SSR2 System status register (2) protection relay's mode and state Table 60: SSR2 System status register (2) protection relay's mode and state RegA Type Scale IEC 61850 name SA name Description Values 129.00 Device test mode 1=Test mode...
Section 2 1MRS757464 C Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values 130.13 < reserved > 130.14 < reserved > 130.15 < reserved > 2.4.1.20 SSR4 System status register (4) data available 2 (client-dependent, user-definable) Table 62: SSR4 System status register (4) data available 2 (client-dependent, user-definable) RegA...
Section 2 1MRS757464 C Modbus data mappings 2.4.1.22 SSR6 System status register (6) control command status (client- dependent) Table 64: SSR6 System status register (6) control command status (client-dependent) RegA Type Scale IEC 61850 name SA name Description Values Last cmd result code 133.00 - bit 0 133.01...
Section 2 1MRS757464 C Modbus data mappings 2.4.1.25 User-definable bits [Alt.2], visible on 0x,1x,3x and 4x Table 67: User-definable bits [Alt.2], visible on 0x,1x,3x and 4x BitA Type Scale IEC 61850 name SA name Description Values < not mappable - not visible > Usr reg 1.Bit 01 Usr reg 1.Bit 02 Usr reg 1.Bit 03...
Section 2 1MRS757464 C Modbus data mappings 2.4.1.28 LD0.CMMXU1 Phase current demand values (1) Table 70: LD0.CMMXU1 Phase current demand values (1) RegA Type Scale IEC 61850 name SA name Description Values LD0.CAVMMXU1 Demand value 2001 1000 .A.phsA.cVal.mag.f I_DMD_A Phs A amplitude 0.00…50.0 [×In] 2002...
Section 2 1MRS757464 C Modbus data mappings RegA Type Scale IEC 61850 name SA name Description Values 1000 .A.phsA.cVal.mag.f Max demand IL1 Phs A amplitude 0.00…50.0 [×In] 1000 .A.phsB.cVal.mag.f Max demand IL2 Phs B amplitude 0.00…50.0 [×In] 1000 .A.phsC.cVal.mag.f Max demand IL3 Phs C amplitude 0.00…50.0 [×In]...
Section 2 1MRS757464 C Modbus data mappings 2.4.2 Unmapped registers Unmapped registers are register data that have no initial Modbus mapping locations, but can be added to the user-definable Modbus area using the Communication Management tool in PCM600. The initial register type settings of these objects have little meaning, since it is always possible to redefine the settings completely for the user-definable register.
Section 2 1MRS757464 C Modbus data mappings IEC 61850 name SA name Description Values 2069 2.09 .RcdRs.Oper.ctlVal Reset Max current1 demands 1=Reset LD0.RESCMMXU1 2073 2.13 .RcdRs.Oper.ctlVal Reset Io (1) max demands 1=Reset 2.5.2 CTRL.CBCSWI1 Circuit breaker control (1) Table 80: CTRL.CBCSWI1 Circuit breaker control (1) IEC 61850 name SA name...
Section 3 1MRS757464 C Glossary Section 3 Glossary Electromagnetic compatibility International Electrotechnical Commission IEC 61850 International standard for substation communication and modeling Intelligent electronic device Light-emitting diode LHMI Local human-machine interface PCM600 Protection and Control IED Manager WHMI Web human-machine interface REM611 Point List Manual...