Product Description The Vent-Axia HR500 and HR500X are heat recovery units for through the wall installation, which extract stale air and as it does so, a heat exchanger within the unit transfers up to 70% of the heat to the freshing incoming air.
Page 4
Product Description Exploded View of Fan Unit and Dimensions HR500 and HR500X Installation & Wiring Instructions...
When taking delivery of the unit, check the items delivered against the enclosed delivery note. Inspect the unit for damage in transit. If in doubt, contact Customer Services. Each box contains an HR500 unit and an accessory pack, energy rating labels and product documentation.
5-core 0.75mm cable and it must be round with a diameter of between 7 and 10 mm to suit the supply cable gland (i.e. the largest gland) in the terminal box. HR500 and HR500X Installation & Wiring Instructions...
Page 7
14. Working from outside, position the divider board in the channel between the fan housings by folding the edges down. Cut the board such that it extends beyond the end of the outer case by 55mm for the HR500 type and falls short of the end of the outer case by 13mm for the HR500X type (see Fig.5).
Page 8
Axia Controller to the appropriate terminals of the terminal block within the terminal box as shown in Fig. 9. If a Vent-Axia Controller is not used, connect the supply cable as shown in Fig. 10. Ensure all cable glands are tightened sufficiently to seal onto the cables.
Page 9
Installation HR500 and HR500X Installation & Wiring Instructions...
DURING MAINTENANCE. Maintenance Heat recovery units require regular maintenance. The HR500 and HR500X has been designed to facilitate access to enable maintenance to be carried out easily. The actions below should be carried out at least every 6-months as conditions dictate.
Position and description of visual filter warning for RVUs intended for use with filters, including text pointing out the importance of regular filter N/A N/A changes for performance and energy efficiency of the unit For UVUs (Instructions Install Regulated Supply/Extract Grilles Façade) N/A N/A Internet Address (for Disassembly Instructions) www.vent‐axia.com www.vent‐axia.com Sensitivity p. Variation@+20/‐20 Pa: (for Non‐Ducted VUs) TBC TBC Air Tightness‐ID/OD‐(m3/h) (for Non‐Ducted VUs) TBC TBC Annual Electricity Consumption: AEC (kWh/a) 7.60 8.31 Annual Heating Saved: AHS (kWh/a) AHS: Average 38.49 38.49 AHS: Warm 17.41 17.41 AHS: Cold 75.30 75.30 HR500 and HR500X Installation & Wiring Instructions...
Page 12
For details of guarantee outside the United Kingdom contact your local supplier. Vent-Axia guarantees its products for two years from date of purchase against faulty material or workmanship. In the event of any part being found to be defective, the product will be repaired, or at the Company’s option replaced, without charge, provided that the product: ...