Page 3
The Toshiba products listed in this document are intended for usage in general electronics applications (computer, personal equipment, offi ce equipment, measuring equipment, industrial robotics, domestic appliances, etc.). These Toshiba products are neither intended nor warranted for usage in equipment that requires extraordinarily high quality and/or reliability or where a malfunction or failure may cause loss of human life or bodily injury (“Unintended Usage”).
Page 4
Unless otherwise specifi ed, the warranty period for the UPS or UPS part is 36 months from the shipment date (see Toshiba International Corporation bill of lading). Unless otherwise specifi ed, the warranty period for a UPS battery is 24 months from the shipment date (see Toshiba International Corporation bill of lading).
Page 5
Toshiba International Corporation reserves the right, without prior notice, to update information, make product changes, or discontinue any product or service identifi ed in this publication. Toshiba is a registered trademark of the Toshiba Corporation. All other product or trade references appearing in this manual are registered trademarks of their respective owners.
Ground Symbol indicates the location of the equipment grounding conductor. Electrical - Voltage & Shock Hazard Symbol indicates parts inside may cause electric shock. Explosion Hazard Symbol indicates parts may explode. 1600EP Series Instruction Manual...
The word ATTENTION in capital letters without ATTENTION the safety alert symbol indicates a potentially hazardous situation exists, if not avoided, may result in equipment and property damage. 1600EP Series Instruction Manual...
288Vdc 288Vdc Servicing of the batteries should only be performed by a qualifi ed Toshiba Representative who is knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries. To arrange for battery replacement, contact your nearest Toshiba authorized service center.
Page 11
Misuse of this equipment could result in human CAUTION injury and equipment damage. In no event will Toshiba Corporation be responsible or liable for either indirect or consequential damage or injury that may result from the use of this equipment.
The unit’s batteries begin to recharge so they will be ready for the next power interruption. Application and Use Toshiba’s 1600EP Series of on-line uninterruptible power system (UPS) systems provide continuous computer-grade AC power in a compact, high performance, and energy effi cient unit. The UPS unit assures safe and reliable operation of critical offi...
It is illegal to dump lead-acid batteries in landfi lls or dispose of improperly. Please help our Earth by contacting the environmental protection agencies in your area, the battery manufacturer, or call Toshiba toll-free at (800) 231-1412 for more information about recycling. 1600EP Series Instruction Manual...
3 Always ground the unit to reduce the potential for electrical shock and to help reduce electrical noise. 4 A separate ground cable should be run inside the conduit with the input power, output power, and control circuits. WARNING THE METAL OF CONDUIT IS NOT AN ACCEPTABLE GROUND. 1600EP Series Instruction Manual...
Wait for at least the minimum time indicated on the label and ensure that the CHARGE LED has gone out before opening the door of the UPS once the UPS power has been turned off. 8 DO NOT attempt to disassemble, modify, or repair the UPS. Call your Toshiba sales representative for repair information.
UPS operation Closed during inverter operation Power failure signal Closed at power failure NOTE Pin “switches” are shown in their inactive states. For example, if battery voltage is low, pin 7 will be connected to pin 5. 1600EP Series Instruction Manual...
UPS STOP SIGNAL FROM OS continues output UPS output voltage CONTINUES OUTPUT UPS OUTPUT VOLTAGE Checking time CHECKING TIME Temporarily cuts off TEMPORARILY CUTS OFF the output for 10 to THE OUTPUT FOR 10 TO 20 SECONDS 20 secs 1600EP Series Instruction Manual...
Clear to send This pin is not used RemotEye Network Card The RemotEye is an optional network card for Toshiba UPS. This card slides into a slot located on the back side (pages 52-53) of the UPS. The card provides a network, or LAN-based communication interface for the UPS.
< ±8% (Load of 0 to 100 %) Rated Output Current (rms) 15.0 A 25.0 A 33.3 A Max. Peak Output Current 45.0 A 75.0 A 100.0 A Inverter Overload Capacity 125%-30 sec/150%-10 sec Bypass Overload Capacity 125%-10 min./1000%-1 cycle Crest Factor 1600EP Series Instruction Manual...
Page 21
Del/Page Down, Reset/Page Buzzer Volume Low, High, Mute; Selectable by keypad Power Connections Hard wire (Standard) Emergency Power Off Standard (Terminal contacts only) Remote Contacts Standard (INV, BYP, BATT, LB, AC, FLT) RS232 ASCII Interface Standard 1600EP Series Instruction Manual...
Page 22
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation (****) At 6600 ft (2000 m) above sea level, output capacity should be derated by 3%. 1600EP Series Instruction Manual...
Page 23
Rated Output Current (rms) 41.6 A 58.0 A 75.0 A 91.6 A Max. Peak Output Current 125 A 174 A 225 A 275 A Inverter Overload Capacity 125%-30 sec/150%-10 sec Bypass Overload Capacity 125%-10 min./1000%-1 cycle Crest Factor 1600EP Series Instruction Manual...
Page 24
Del/(page down), Reset/(page Buzzer Volume Low, High, Mute; Selectable by keypad Power Connections Hard wire (Standard) Emergency Power Off Standard (Terminal contacts only) Remote Contacts Standard (INV, BYP, BATT, LB, AC, FLT) RS232 ASCII Interface Standard 1600EP Series Instruction Manual...
Page 25
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in operation (****) At 6600 ft (2000 m) above sea level, output capacity should be derated by 3%. 1600EP Series Instruction Manual...
To stop the UPS, press the STOP key approximately 1 second until the LED changes from green to “off”. The UPS is now in the bypass mode. To completely stop the UPS, turn the input breaker at the back of the UPS to the “OFF” position. 1600EP Series Instruction Manual...
The following chart shows the rated maximum and minimum battery voltages and the charge current for each of the sizes. RATED BATTERY VOLTAGES Model Vmax Vmin Icharge 3.6kVA 245.7 1.0 amp 6kVA 245.7 1.0 amp 8kVA 1.0 amp 10kVA 1.0 amp 14kVA 1.0 amp 18kVA 1.0 amp 22kVA 1.0 amp 1600EP Series Instruction Manual...
Isolation Transformer MCCB Output Input fuse fuse Input Rectifier/ Output Inverter Line Filter Line Filter power Chopper power Surge absorber *Switches are Batteries solid state devices Power flow POWER FLOW IN BYPASS MODE FOR ALL MODELS 1600EP Series Instruction Manual...
EPO switch is the same whether the UPS unit is in the Bypass *Static switch TRIPPED Isolation Transformer MCCB Output Input fuse fuse Input Rectifier/ Output Inverter Line Filter Line Filter power Chopper power (off) Surge absorber *Switches are Batteries solid state devices Power flow 1600EP Series Instruction Manual...
Shift The audible alarm can be silenced by pressing key on the front panel (see page 32). Select AUDIBLE ALARMS Condition Audible Pattern UPS in battery Backup mode UPS low Battery voltage Overload 0.5S 0.5S Fault 1600EP Series Instruction Manual...
This information is determined by the UPS operating mode and conditions. These messages are shown in the LED displays and LCD screens on pages 33 through 46. 1600EP Series Instruction Manual...
Lights in amber Warning Flashes in amber Warning LED “OFF” (Stop) Normal UPS (Inverter) in operation Lights in green Schedule/timer setting Execution notice of reserved operation (5 mins. in Flashes in green advance) LED “OFF” No schedule/timer setting 1600EP Series Instruction Manual...
UPS capacity being supplied. Initially, the UPS is in bypass mode, and the following screen will appear: BYPASS OPERATION LOAD###% NOTE: If input voltage is removed while UPS is in the Bypass Mode then the output stops. 1600EP Series Instruction Manual...
Page 35
BATTERY TEST BAT VOLTAGE ##% Once the battery test has concluded, the LCD will return to display of the current UPS operation mode and percent load. It should appear as follows: UPS OPERATION LOAD ###% 1600EP Series Instruction Manual...
INTERNAL TEMP ## C 11/4/1998 10:45 TIMER START DATA TO VIEW:SELECT TIMER STOP DATA TO VIEW: SELECT CAL OPER MODE DISABLE WEEKLY SCHDULE TO VIEW: SELECT SPECIAL OPERATE TO VIEW: SELECT SPECIAL OPERATE TO VIEW: SELECT 1600EP Series Instruction Manual...
###.## - ###.## NOTES 1 To access the data setting screens pess the “SET/MONITOR” key from any of the (see page 38) Data Settings Screens. 2 Pressing the “SHIFT/SELECT” and “CANCEL” key returns to the Data Display Screens. 1600EP Series Instruction Manual...
Page 38
TO CHANGE:SELECT INI BAT TST: YES TO CHANGE:SELECT AUTO BATT TST: NO TO CHANGE:SELECT BATTERY TEST DATA SET: SELECT PERFORM BAT TEST PUSH SELECT VOLTAGE ADJ: +0 TO CHANGE:SELECT CLEAR TIMER SET DEFAULT SETTINGS PUSH: SELECT 1600EP Series Instruction Manual...
Page 39
Default setting is NO. TO ACCEPT:SET TO CHANGE: SELECT Monitor Select Shift AUTO RUN: NO AUTO RUN: NO TO ACCEPT:SET TO CHANGE:SELECT Monitor Select Returns to Data Setting Loops through both Screens (with new value possibilities applied) 1600EP Series Instruction Manual...
Page 40
Shift INI BATT TST: NO INI BATT TST: NO TO CHANGE:SELECT TO ACCEPT:SET Monitor Default setting is NO. Select Returns to Data Setting Loops through both Screens (with new value possibilities applied) 1600EP Series Instruction Manual...
Page 41
FOR NEXT:SELECT Monitor Select values applied) At any time all of the preceding operations can be canceled by pressing SHIFT + Loops through all hours CANCEL. Canceling returns to the 'Data of the day Setting Screens' menu. 1600EP Series Instruction Manual...
Page 42
INTERVAL: 2DAY INTERVAL: 2DAY TO ACCEPT: SET TO CHAGNE:SELECT Monitor Select Shift INTERVAL: 99DAY INTERVAL: 99DAY TO ACCEPT: SET Monitor TO CHANGE: SELECT Select Returns to Data Settings Screens (with new value applied) Loops through 99 possibilities 1600EP Series Instruction Manual...
Page 43
Executes battery test timer setting. and returns to Data Settings Screens Shift DEFAULT SETTINGS DEFAULT SETTINGS TO CHANGE:SELECT TO ACCEPT: SET Monitor Select Executes battery test and returns to Data Settings Screens 1600EP Series Instruction Manual...
Otherwise, shut down the unit and call for service. Meaning: Advance notice that batteries are nearing the end of the expected lifetime. Amber REPLACE BAT Action: Contact your Toshiba authorized SOON Flashes service center to arrange for battery replacement. Amber Meaning: Batteries at end of life.
40° C or OVERHEAT greater.Bypass operation will also cease if overheat condition is not corrected within 1 hr. Flashes from inverter shutdown. Try restarting and if condition re-occurs plan for total shutdown and call for service. 1600EP Series Instruction Manual...
Action: None required. Meaning: When the key lock is set or the timer is set to start/stop the UPS by data KEY LOCK:EN communication, pressing the RUN or STOP key displays this message. Action: None required. 1600EP Series Instruction Manual...
Bypass OL: fault lamp “on” Fault relay open; Relay Contact Fault relay closed; Inverter OL: Bypass relay closed Alarm Bypass relay closed Bypass OL: Bypass relay open Inverter OL: Yes if bypass is OK Auto-retransfer Bypass OL: No 1600EP Series Instruction Manual...
Page 48
Chopper and inverter are stopped After Fault Inverter OL: Transfer to bypass; Audible Alarm Yes; continuous buzzer Yes; continuous buzzer Visible Alarm Red Fault LED “on” Red Fault LED “on” Relay Contact Fault relay closed; Bypass relay closed Alarm Auto-retransfer 1600EP Series Instruction Manual...
Preventive Maintenance/Parts Replacement Preventive Maintenance Toshiba’s 1600EP Series of uninterruptible power systems have been designed to provide years of trouble-free operation requiring a minimum of preventive maintenance. The best preventive measure that the UPS user can take is to keep the area around the unit, particularly the air inlet vents, clean and free of moisture and dust accumulations.
Step 3: Mount the receptacle panel Attach the screws removed from the cover plate through the mounting holes of the receptacle panels and back into the UPS mounting points. Mounting Screws Figure 1 Figure 2 1600EP Series Instruction Manual...
2.7 in 3.47 in 3.47 in 3.47 in (72 mm) (72 mm) (72 mm) (72 mm) (88 mm) (88 mm) (88 mm) Shipping Weights SHIPPING WEIGHTS Model Pounds Kilograms 3.6kVA 6kVA 8kVA 10kVA 14kVA 18kVA 22kVA 1600EP Series Instruction Manual...
Page 52
External Layouts * 1600EP Series Instruction Manual...
Page 53
External Layouts * (cont’d) Display Remote Remote Panel Contacts Contacts SNMP SNMP Port Port Cooling Fans Terminal Block Cover MCCB Front View Back View Back View 14/18 kVA 10 kVA Side View Flow 1600EP Series Instruction Manual...