  • Page 1 Grid Automation Products SAM600 Process Bus I/O System Version 1.2 Engineering manual...
  • Page 3 Document ID: 1MRK 511 433-UEN Issued: May 2019 Revision: B Product version: 1.2 © Copyright 2017 ABB. All rights reserved...
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software and hardware described in this document is furnished under a license and may be used or disclosed only in accordance with the terms of such license.
  • Page 5 This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
  • Page 6 (Low-voltage directive 2014/35/EU). This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standard EN 60255-27 for the low voltage directive. The product is...
  • Page 7 Safety information Observe the following safety instructions when using the product. Before first usage, read the product documentation in order to ensure safe and reliable operation of SAM600 products. Dangerous voltages can occur on the connectors, even though auxiliary voltages are disconnected. Each SAM600 product must be safely connected to ground using the ground strap.
  • Page 9: Table Of Contents

    Importing SCL files to PCM600 ....................35 5.4.2.1 Importing ICD or CID files.......................36 Object properties ..........................36 Miscellaneous SAM600 tools ......................37 5.6.1 Get serial number ........................37 SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 10 IED configuration migration tool ..............49 Migration Procedure........................49 8.1.1 Export and import of project....................49 8.1.2 IED configuration migration (ICM)..................50 Section 9 Glossary......................53 Section 10 SAM600 parameter settings................55 SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 11: Introduction

    SAM600 1.2 PICS and PIXIT (IEC61580 Ed1) 1KHL516076 SAM600 1.2 MICS (IEC61850 Ed2) 1KHL516090 SAM600 1.2 IEC/IEEE 61850-9-3 PICS 1KHL516091 SAM600 1.2 TICS (IEC61850 Ed2) 1KHL516092 SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 12: Symbols And Conventions

    • Parameter names are shown in italics. Operation setting. For example, the function can be enabled and disabled with the SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 13: Engineering Tool Set

    In simple cases, default values meet the customer specifications. In the System Configuration Tool, the system engineer creates sample value links and customizes the details of single-line SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 14: Sam600 System Configuration With Pcm600

    Event Viewer Tool, see Section • Interact with SAM600 system via commands, see Section 5.6. IEC18000104 V1 EN-US Figure 1: Organization of PCM600 in different management tasks SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 15 Conversely, engineering information can be uploaded from a SAM600 system for various purposes. The connection between the physical SAM600 system and PCM600 is established via USB link. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 17: Engineering Process

    SAM600 system bus, and creating the Access Points Parametrization Sampled value and port configuration Write to Write SAM600 IED IEC18000105 V1 EN-US Figure 2: SAM600 system engineering workflow SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 19: Setting Up A Project

    A plant structure is used to identify each SAM600 system in its location within the substation organization. It is a geographical image of the substation and the bays within the substation. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 20 Right-click on the Plant Structure select New, General and select either SAM600 MU Group or Substation Click View in the menu bar and select Object Types. Select the required elements and drag and drop them into the Plant Structure. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 21: Instantiating A Sam600 System

    Right-click on the Bay, navigate to New and select SAM600 MU application type. Select and click a SAM600MU, see Figure 5. A SAM600 MU Configuration Wizard dialog box appears. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 22 IEC18000109 V1 EN-US Figure 6: PCM600: Configuration mode selection wizard Select USB from the IED protocol drop-down list, see Figure For SAM600, only USB IED protocol is supported. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 23 Port Selection drop down list. Click the Scan button to scan or read the SAM600 product version for a SAM600 system that is online, see Figure SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 24 Based on the physical topology, SAM600 system can either be connected in daisy chain or ring system. Click the Next button to open a SAM600 system Access Point Selection page, see Figure SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 25 Finish button. IEC18000115 V1 EN-US Figure 12: PCM600: SAM600 system Setup completion wizard If an error occurs, cancel the insertion and reinsert a SAM600 system into PCM600. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 26: Inserting A Sam600 System In Offline Mode

    Select the Offline Configuration radio button, see Figure IEC18000651 V1 EN-US Figure 13: PCM600: Configuration mode selection wizard Select USB from the IED protocol drop-down list, see Figure SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 27 The selected port will be used later to write the configuration to the SAM600 system. Select the available product version from the Version Selection Page, see Figure SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 28 The amount of analog processing modules (SAM600-CT, SAM600-VT) per SAM600 system is limited to 7. The amount of time synchronization modules (SAM600-TS) is limited to 3 per SAM600 system. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 29 Name, Physical Port A, and Physical Port B (available if the redundancy Mode is either HSR or PRP). IEC18000691 V1 EN-US Figure 19: SAM600: Access Point selection page wizard Redundancy is supported only on SAM600-TS module and not on other modules. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 30: Technical Key

    The technical key property in PCM600 corresponds to a SAM600 system name attribute in SCL files. Changing a SAM600 system name attribute value outside PCM600 may cause the loss of data when SCL files are imported. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 31 Use the existing technical key defined for a SAM600 system object in PCM600 • Set a user defined technical key, which changes the technical key for both the physical SAM600 system and SAM600 system object in PCM600 SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 32: Sam600 Serial Numbers

    Get Serial Number command at a SAM600 system level (only in online mode) If the entered serial number is incorrect, the appropriate validation errors are displayed. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 33: Sam600 Engineering

    PCM600 can be modified using PST. To export parameters from PST, both XRIO and CSV file formats are supported. IEC18000653 V1 EN-US Figure 23: Parameter Setting Tool SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 34: Sam600 System Parameters

    During the Common Write action, both basic and advanced settings are written to a SAM600 system. A SAM600 system supports up to three PTP access points. Each module supports up to one PTP access point. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 35: Sam600 Sv Stream And Port Configuration

    PCM600 tool which can be launched from a SAM600 system context menu, see Figure 25. It is possible to subscribe external SV streams and to publish those over available SAM600 ports. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 36 Figure IEC18000656 V1 EN-US Figure 26: Add SV Streams in Content Definition The options that are available when a stream is added is shown in Table SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 37 Figure IEC18000658 V1 EN-US Figure 28: Add SV Stream in Source Port Assignment Configure the SV streams that need to be bridged. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 38 A SAM600 module cannot use more than eight source streams for its configured sent streams. For more details, see SAM600 Operation manual . A SAM600 module can be configured to send up to 10 streams. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 39: Composition Upgrade Tool

    An existing SAM600 configuration can be modified, extended or updated at any time. This is achieved using Composition Upgrade Tool which can be launched from a SAM600 system context menu, see Figure SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 40 The user will be informed and asked to confirm the update, see Figure IEC18000664 V1 EN-US Figure 33: System consistency update by changed system configuration SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 41: Exporting And Importing Scl Files

    Click the Export button to export SCD file to the chosen location. 5.4.1.2 Exporting ICD or CID files GUID-66B25CAA-6CFB-4FD2-8DC2-E857B1C1250C v1 Follow the procedure to export ICD or CID files from PCM600: SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 42 SAM600 system at runtime. • IED Capability Description (*.icd) is used for the IEC 61850 structure. Click the Save button. The SCL Export Options window appears, see Figure SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 43: Importing Scl Files To Pcm600

    PCM600 is able to import SCD, ICD and CID files. All SCL files imported in PCM600 must include the original subnetwork of type "ABB-USB". In case a System Tool will remove this subnetwork the SCD import will fail or be refused by PCM600.
  • Page 44: Importing Icd Or Cid Files

    Similarly, when Plant Structure is expanded and objects under it are selected, its properties are also shown in the Object Properties section, in which some of the field values are editable. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 45: Miscellaneous Sam600 Tools

    This sets the system time on SAM600-TS module of a SAM600 system to the local PC time. This menu appears if there is at least one SAM600-TS is available in a SAM600 system. IEC18000670 V1 EN-US Figure 39: PCM600: Set Time SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 46: Simulation Mode

    Figure 40: PCM600: SAM600 System Simulation Mode In this state the SAM600 modules will simulate nominal analog values with the configured transducer ratio settings per phase. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 47: Reset To Factory Default

    Indicate Module action can be launched from the module context menu. This tool identifies the physical hardware module in a SAM600 system. When Indicate Module option is selected, LEDs on the corresponding hardware module flashes for 20 seconds. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 48 Section 5 1MRK 511 433-UEN B SAM600 Engineering This command can also be launched from Get Serial Number tool. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 49: Communication With Pcm600 And Sam600 System

    Once a SAM600 system engineering is completed, the system writes the configuration to a SAM600 system. Perform Common Write action from a SAM600 system context menu by selecting Write to IED…option, see Figure SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 50 Common Write is aborted and the appropriate error message is displayed on the PCM600 output window. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 51: Common Read

    SAM600 system configuration context menu to identify all the modules in the SAM600 system. Common read GUID-05BF930D-FA65-4332-B075-83981AD4553C v1 Perform Common Read from a SAM600 system context menu by selecting Read from IED… option, see Figure SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 52 Number of SAM600 modules • Type of SAM600 modules • Serial Number • Order of SAM600 modules • Interconnection between SAM600 modules • Configuration existence in SAM600 system SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 53 PCM600 output window. Common Read cannot be performed on modules that has factory default values. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 55: Event Viewer Tool

    Read Event per Module property under Misc tab in the Object value need to be set in the Properties window. IEC18000678 V1 EN-US Figure 49: EVT object properties For more information, refer to PCM600 online help. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 57: Ied Configuration Migration Tool

    Make an export of the project that need to be migrated by selecting Open/Manage project Mark the project that need to be exported and select Export Project Install the type data modules versions to which migration needs to be done (e.g. ABB SAM600 module version 1.2.0.0). Open PCM600...
  • Page 58: Ied Configuration Migration (Icm)

    GUID-8925C7B0-F6F9-44C3-BD22-8F15C3E83F51 v1 Select the IED to migrate and right click migrate configuration Select the version to migrate to (e.g. 1.2.0) in the Dialog and press continue. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 59 Various steps during migration process is indicated in the following screen and the migration process will take some minutes based on the configuration. At the end, a dialog will confirm that the migration is completed. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 60 Make sure that Show IED Configuration Migration Report check box is selected, so that the migration report can be either saved or printed later. The PCM600 output window will contain valuable information related to the migration. SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 61: Glossary

    System Configuration Description Language System Configuration Tool Small Form factor Pluggable SMVID Sample Value Identifier System Specification Tool Sample Value Universal Serial Bus Coordinated Universal Time SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 63: Section 10 Sam600 Parameter Settings

    Module Type SAM600-CT and SAM600-VT Level SAM600 Module Value Range SAM600-CT-1 (constant) SAM600-CT-5 (constant) SAM600-VT: {100, 110, 115, 120, 125} Default SAM600-VT: 110 SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 64 Parameter Allowed Inaccuracy Unit Description The system time inaccuracy in relation to reference clock. Module Type Level SAM600 System Value Range 1, 4 µs Default µs SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 65 AA0B0Q0KF0 Parameter Customer-provided name to identify the individual SAM600 module Description Designator of a module. Module Type Level SAM600 Module Value Range String[48] Default empty string SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 66 Globally unique SAM600 identification. Module Type Level SAM600 Module Value Range String [10] First two characters are alphabets and remaining are 8 digits. Default empty string SAM600 Process Bus I/O System Engineering manual © Copyright 2017 ABB. All rights reserved...
  • Page 68 ABB AB Grid Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 Scan this QR code to visit our website www.abb.com/protection-control © Copyright 2017 ABB. All rights reserved.