Cables

• Select the input power cables as described in the appropriate drive Hardware
Manual. The cross-sectional area of the DC cables must be the same as the
cross-sectional area of the AC side cables.
• If screened DC cables are used, ground the screen at the other end only.
• The lengths of the supply cables must not differ more than 15%. This applies
especially to converters equipped with DC chokes.
• Maximum length of the DC cables between two converters is 50 m.
• If the system consists of more than two converters, the DC links must be
connected in an external terminal box. Do not use the terminals of one of the
converters for this purpose.
Design