User Definable Text Messages (Alarm Texts) - Panasonic Alert annunciation unit 1736 Technical Description

Table of Contents

Advertisement

7

User definable text messages (alarm texts)

In the C.I.E., each alarm point (zone – address) and each zone can have an
individual user definable text message (alarm text)
by fire alarm, see the Technical and Operation Manuals for the system
respectively.
The user definable text messages shown in the C.I.E. will also be sent to each
Alert Annunciation Unit and shown in its display.
As an alternative, text messages for all or selected alarm points / zones can
be stored in each AA unit.
of the text messages sent out from the C.I.E.
The priority order is as follows:
1.
Point alarm text stored in the AA unit.
2.
Zone alarm text stored in the AA unit.
3.
Default alarm text stored in the AA unit.
4.
Text sent out from the C.I.E.
When alarm texts shall be stored in all or in some AA units, the unique alarm
texts are created in Win512 / Win128 / WinG3 and downloaded when the
C.I.E. site specific data (SSD) is downloaded.
NOTE! It is also possible to select which fire alarms that shall be presented in
the AA unit respectively, see chapter "Selective Fire alarm presentation", page
8.
13
Each alarm text (up to 40 alphanumeric characters) will be shown on the second
row. The text messages are created and downloaded via Win512 / Win128 / WinG3.
14
At least 617 text messages can be stored in each unit.
14
If so, these text messages will be shown instead
16
Technical Description
AAU 1736 – Rev 1
13
presented in the display