Control and indicating equipment eblone (33 pages)
Summary of Contents for Panasonic External Presentation unit 1728
Page 1
Technical Description MEW01297 Revision 2 External Presentation unit 1728, ver. 1.4.x Author: Jan Pettersson Date of issue: 2010-04-08 Date of rev: 2011-08-15...
Page 2
This page has deliberately been left blank.
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Table of contents Introduction________________________________ 3 Definitions / Explanations ____________________ 4 General description _________________________ 5 Ext. Presentation Unit 1728 __________________________ 5 3.1.1 SW mode 1728 - 1587 ___________________________ 5 3.1.2...
Page 4
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Revision history ____________________________ 33 This page has deliberately been left blank.
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Introduction This document describes the External Presentation unit 1728 (Informationstablå). The shorter expression EPU will also be used in this document. The 1728 unit can run in one of two SW modes:...
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Definitions / Explanations Definitions / explanations / abbreviations / etc. frequently used or not explained elsewhere in the document. External Presentation Unit C.i.e. Control and indicating equipment (=control unit) C.U.
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x General description The ext. Presentation unit is intended for pre-warning, co-incidence, fire and heavy smoke / heat alarm presentation. Any fault in the system will be presented as "General fault in system".
Page 8
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x display 2428SE. Note, the functionality / performance is the same but the size, the look and the front layout are different. In system EBL512, 1728 units running in SW mode 1728 – 1582 have to be connected to an Ext.
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Selective alarm presentation Normally all fire alarms will be presented in the c.i.e:s, ext. FBPs and Presentation units, etc. There are some possibilities to select which alarms that shall be presented in each unit.
Page 10
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Default in systems EBL512 and EBL512 G3 is: Control units (00, 29), i.e. all alarms from all c.i.e:s will be presented in all ext.
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x LED indicators, Push buttons, etc. The functions of the LEDs, push buttons, display and buzzer are described below. Ext. Presentation Unit 1728 Figure 2.
Page 12
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Table of LED indicators: LED indicator Colour Indicating Fire (Brand) 2 x Red Blinking+ Fire alarm. (Also indicating heavy Buzzer smoke / heat alarm the same way as in (interm.)
Page 13
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Table of push buttons: Push button Colour Operation / function Alarms queued Used, when LED "L2" (Alarms queued) is turned on, Black to scroll through the queued alarms. (The first alarm...
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x SW mode & Address setting Each Ext. Presentation unit can in system EBL512 run in SW mode 1728 - 1587 or SW mode 1728 – 1582, i.e. it can be used as two different types of units.
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x NOTE! If the stored SW mode is 1728 – 1582 a language has to be set before the address can be set . The following information will be shown in...
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x For an ext. Presentation unit with SW mode 1728 - 1587, the address can be set to 00-15. (Default is "00".) For an ext. Presentation unit with SW mode 1728 - 1582, the address can be set to 01-08.
Page 17
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Power on / Restart / Reset via "JP1" "J4" ON? SW mode selected? SW mode setting Normal operation Address SW mode command from xxxx - 1587? c.i.e.
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x User definable text messages (alarm texts) The user definable text messages (alarm texts) are depending on which mode the unit is running in. In SW mode 1728 - 1587 In the c.i.e., each alarm point (zone –...
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Commissioning a new unit / SSD download The cable (RS485 line) to the ext. Presentation unit(s) shall be connected. In the EBL512 c.i.e. the 1582 / 1587 board shall be mounted. Remove the fuse "F1"...
Page 20
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x 7. When the download of SSD to the c.i.e. is finished, it will restart. Then the download of SSD to the ext. Presentation unit(s) will take place.
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Restart The ext. Presentation unit will restart: When it is powered up If the jumper "JP1" is shunted momentarily After address setting (i.e. after "P2" is pressed).
Page 22
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x If there is an SSD (Site Specific Data) memory fault or no SSD downloaded, there will be a fault message in the display: "SSD memory fault"...
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Fault messages The buzzer will sound continuously for any not acknowledged fault in the system or a fault in the unit. The buzzer will be silenced when all faults are acknowledged (in any c.i.e.) or with the push button "P2"...
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x "FAULT: Comm, EPU xx, 1587 board x, CU xx" The contact with the ext. Presentation unit is interrupted. Check the cable, all connections and the 1582 / 1587 board. Is a correct / complete SSD download (via Win512) performed? Check the address setting (1582 / 1587 board / the ext.
Page 25
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x "FAULT: Site specific data, external presentation unit xx, Control unit xx" See chapter "Restart", page 19.
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Disablement message Any disablement in the system, i.e. when the LED "Disablements" in any c.i.e. is turned on, will be displayed as "General disablement in system"...
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Software (S/W) The software is stored in a flash memory in each ext. Presentation unit. This software can be replaced / updated (i.e. downloaded via Win512 / Win128 / Win512 G3).
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x 5 The ext. Presentation unit will restart (Restarting..), i.e. the buzzer will sound for approx. two seconds and the unit will return to normal operation.
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Operation In normal operation (quiescent condition) the LED "L6" (Operation) is turned on, the display is blank (back-light off) and the buttons are not possible to use.
Page 30
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Figure 3. Operation summary for the Ext. Presentation Unit 1728. (Co-incidence alarm = 2-zone / -address dependence.). The buzzer sounds continuously for any not acknowledged fault in the system and "Silence buzzer"...
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Connections The ext. Presentation unit is equipped with a plug-in terminal block (J1:1-8) for the cable connections. Up to 1.5 mm conductor area can be used.
Page 32
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Comments to the components: 1.5 A fuse (not replaceable, i.e. the whole p.c.b. has to be replaced). Terminal block for the ext. Presentation unit connections.
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Technical data 15.1 Power supply Nominal voltage for the Ext. Presentation unit 1728 is 24 V DC. The number of Ext. Presentation units that can be power supplied from the c.i.e.
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x 15.5 Current consumption The current consumption is depending on the actual voltage on the line. The following table shows the current consumption for the unit in relation to the actual line voltage (min.
Page 35
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x Revision history Revisions are, when possible, written with red font colour. Revision 1 Info. revised. Info. added in footnote 6. Info. revised and added.
Page 36
Panasonic Electric Works Nordic AB MEW01297 Rev: 2 Technical Description External Presentation Unit 1728, ver. 1.4.x...
Page 37
This page has deliberately been left blank.
Page 38
Panasonic Electric Works Nordic AB Jungmansgatan 12, SE-211 19 Malmö, Sweden Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info-fste@eu.pewg.panasonic.com • www.panasonic-fire-security.com...