Accuracy - LSIS XBF-AD04A User Manual

Analog programmable logic controller
Hide thumbs Also See for XBF-AD04A:
Table of Contents

Advertisement

XGB Analog edition manual

12.5 Accuracy

Accuracy / Resolution are as follows according to ambient temperature
Measurement
Thermocouple
temperature
type
-200.0℃ ~
K
1300.0℃
-200.0℃ ~
J
1200.0℃
Note1) Total accuracy (normal temp.) = accuracy (normal temp.) + cold junction compensation accuracy
Cold junction compensation accuracy = ±1.0℃
Note2) Temp. coefficient: ±100 ppm/℃
(1) When ambient temp. is normal (25 ± 5℃): within the ±1% of entire measurement temp. range
(2) When ambient temp. is operating temp. (0 ~ 55℃): within the ±1% of measurement temp. range
Ex.) When K type thermocouple is used and ambient temperature is normal.
In case of measuring 1000℃ temperature, output range of conversion data is
1000℃ - [{1300 - (-200)} x 1 %] - 1 ~ 1000℃ + [{1300 - (-200)} x 1%] + 1
namely, 984.0 ~ 1016.0 [℃] 입니다.
Note
(1) For stabilization of measurement temperature, warming-up time more than 15 min. is necessary, after
restart.
(2) If ambient temperature changes rapidly, measurement temperature may change temporally. Keep the
ambient temperature steady for stabilization of measuring temperature.
(3) If wind of the cooling pan contacts with module directly in the panel, accuracy decreases. Do not
contact with wind directly.
Indication temperature
range
range
-200.0℃ ~ 0.0℃
0.0℃ ~ 1300.0℃
-200.0℃ ~ -100.0℃
-100.0℃ ~ 1200.0℃
= ±(full scale X 0.2% + 1.0℃)
Accuracy - note1)
Normal
temperature
(25℃)
12 - 6
Operating
Resolution
temperature -
note2)
(0℃ ~ 55℃)
±15.0℃
±14.0℃
0.2℃
0.1℃
0.2℃
0.1℃

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the XBF-AD04A and is the answer not in the manual?

Questions and answers

Table of Contents