ControlMaster CM10, CM15, CM30, CM50, CMF160 and CMF310
Universal process controllers and indicator,
...Communication
MODBUS TCP Setup Note. After changing any of the TCP parameters it is advisable to power-cycle the instrument to
Implementation
Port
Connections
Client Authority
Client 1 (to 3) IP
10
1
/
,
8
ensure changes are applied.
Select the MODBUS TCP operation mode:
Off – MODBUS TCP disabled
Server – instrument acts as a MODBUS slave
Displays the TCP/IP port used by the MODBUS TCP network (fixed at 502).
Select the maximum number of simultaneous TCP/IP connections permitted – minimum 1,
maximum 3.
Select the number of authorized TCP/IP connections permitted:
Selected from:
Unrestricted – any MODBUS TCP client device is permitted to poll the instrument
1 (to 3) – Only the MODBUS TCP client device whose IP address is entered in the
authorized Client 1 (to 3) IP parameter (below) is permitted to poll the instrument.
Enter the IP address(es) of the MODBUS TCP Client (MODBUS Master) device(s) permitted to poll
the instrument for data.
Note. Displayed only if the Client Authority parameter (above) is not set to Unrestricted.
1
1
/
,
/
DIN and fieldmount
4
2
4 Communication Level