Panasonic FP0R Series User Manual page 67

Analog i/o unit
Hide thumbs Also See for FP0R Series:
Table of Contents

Advertisement

 0V to 10V DC output (14-bit mode only)
Conversion characteristic
 0V to 5V DC output (14-bit mode only)
Conversion characteristic
KEY POINTS
The following operations are performed when a value exceeding the
allowable range is written. Always insert a program for checking the upper
and lower limits right before a program for writing data.
Mode
Data range
-1 or less
14-bit
mode
---
Including negative value
Including negative value
Description
The bits F and E of a written value may be regarded as
16384 or more
channel switching flags and converted to an unintended
value and output.
The value does not change and the previous value is
16001 to 16383
held.
4.5 I/O Conversion Characteristics
Correspondence table of D/A Conversion
values
Digital value
14-bit
0
4000
8000
12000
16000
Processing if the range is exceeded
Digital input value
16001 or more
Correspondence table of D/A Conversion
values
Digital value
14-bit
0
4000
8000
12000
160000
Processing if the range is exceeded
Digital input value
16001 or more
Output voltage (V)
0.0
2.5
5.0
7.5
10.0
Output voltage (V)
Refer to the following
notes.
Output voltage (V)
0.0
1.25
2.5
3.75
5.0
Output voltage (V)
Refer to the following
notes.
4-41

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Afp0rad4Afp0rad8Afp0ra21Afp0ra42Afp0rda4

Table of Contents