Common Precautions; Wiring Of Analog I/O Unit - Panasonic FP0R Series User Manual

Analog i/o unit
Hide thumbs Also See for FP0R Series:
Table of Contents

Advertisement

Wiring

3.4 Common Precautions

3.4.1 Wiring of Analog I/O Unit

 Wiring diagram
Voltage input
Analog device
*1: For the current input, short-circuit the V and I terminals.
Voltage output
V
I
COM
 Precautions on Wiring
• Use double-core twisted-pair shielded wires. It is recommended to ground the shielding.
However, depending on the conditions of the external noise, it may be better not to ground
the shielding.
• Do not have the analog input wiring close to AC wires, power wires, or load wires.
• Do not have the analog output wiring close to AC wires, power wires, or load wires.
 Compatible cable (twisted wire)
Size
AWG#28-16
 Special tools
Manufacturer
Phoenix Contact Co.
3-8
V
I
COM
Analog device
Nominal cross section area
2
2
0.08 mm
-1.25 mm
Serial number (model number)
SZS0.4×2.5(1205037)
Current input
Analog device
Current output
V
I
COM
*1
V
I
COM
Analog device