2.3.2 Setting of Mode Switch

 Setting of the mode switch
Item
No.
1
2
I/O resolution
and FP0-A21-
compatible
12-bit mode
input range
3
FP0-A21-
4
compatible
12-bit mode
output range
(Note 3)
3
4
14-bit mode
output switch
(Note 4)
Input averaging
5
(Note 1): When the both switch No.1 and No.2 are OFF, the input voltage/current is switched by the connection
method.
(Note 2): In the 14-bit mode, the input and ouput ranges are set by writing into the operation memory WY with a user
program.
(Note 3): The setting of "FP0-A21 compatibility 12-bit mode output switch" of the switches No.3 and No.4 is valid
when the switch No.2 is off.
(Note 4): The setting of "14-bit mode output switch" of the switches No.3 and No.4 is valid when the both switch No.1
and No.2 are on. Switching CH1 is available only for A42 type.
(Note 5): All the switches are set to OFF at the factory.
(Note 6): The switch settings will be valid when the power is turned ON from OFF. The settings will not change if the
operation power supply is switched when it is ON.
Settings
OFF
ON
OFF
OFF
FP0-A21-
compatible
FP0-A21-
compatible
12-bit mode
12-bit mode
0 to 5V/0 to
20mA
-10 to +10V
(Note 1)
OFF
ON
OFF
OFF
FP0-A21-
Reserved
compatible
for system
12-bit mode
(Not settable)
0 to 20mA
OFF
ON
OFF
OFF
CH0 Voltage
CH0 Current
output
output
CH1 Voltage
CH1 Voltage
output
output
OFF: Averaging Not performed, ON: Averaging Performed
2.3 Analog I/O Unit (FP0R-A21/A42)
OFF
ON
Reserved
for system
(Not settable)
OFF
ON
FP0-A21-
compatible
12-bit mode
-10 to +10V
OFF
ON
CH0 Voltage
output
CH1 Current
output
ON
ON
14-bit mode
(Note 2)
ON
ON
Reserved
for system
(Not settable)
ON
ON
CH0 Current
output
CH1 Current
output