SINAMICS S120 Chassis (Motor Modules), continued
Dimension drawing 17, frame size JX:
380 V to 480 V
500 V to 690 V
Side view
Required clearance for ventilation - - - - - -
DC link connection
Cross-section per
Busbar
connection
connection
DIN
VDE
mm²
60 x 60 x 8
560 - 800 kW
710 - 1200 kW
Rear view
Motor connection
Max. cross-section
per connection
DIN
NEC, CEC
VDE
AWG/MCM
mm²
6 x 240
6 x 500
MCM
Dimension Drawings
Engineering Information
Grounding
M12 screw
Max. connection cross-
section
(No. of holes)
DIN
VDE
mm²
(3)
PE1
1 x 240
PE2
2 x 240
SINAMICS Engineering Manual - May 2008
Screw
M12
NEC, CEC
(No. of holes)
AWG/MCM
1 x 500 MCM
(1)
2 x 500 MCM
(2)