Application data

Basic ratings
WavePro
low voltage power circuit breakers are available in
various levels of interrupting capacity (IC) and are identified
with a suffix in the model number. WPS indicates "standard
IC," WPH indicates "high IC," WPX indicates "extended IC" and
WPF indicates "integrally fused."
High IC and extended IC breakers are used with larger kVA
substation transformers as well as in parallelling applications.
Fused circuit breakers take the IC rating to 200kA rms
symmetrical for the highest short circuit applications.
Refer to Table 12.1 for the interrupting capacity (IC) of
WavePro breakers at system operating voltages.
WPS — Standard IC
WPH — High IC
WPX — Extended IC
WPF — Integrally fused (200kAIC)
Table 12.2 Breaker/Sensor/Rating Plug Combinations for Power+™,
and MicroVersaTrip Plus™/PM™
Breaker Frame
Rating (Amps)
Sensor Rating
800
150
800
400
800/1600
800
1600
1600
2000
2000
3200
3200
4000
4000
5000 
5000 
ΠThese rating plugs values are not available on Power+ trip units.
 Power+ trip unit is not available on WPS-50 (5000A) breaker.
Table 12.3 shows the minimum and maximum fuse ratings allowed for WavePro breakers based on the breaker frame size
and rating plug. Maximum fuse ratings protect the circuit breaker under short circuit conditions with up to 200kA available.
Minimum fuse sizes are established based on UL continuous current tests when the fuse is mounted on the circuit breaker.
Table 12.3 Allowable current limiting fuse sizes for WavePro low voltage power circuit breakers (600Vac Max, 50/60 HZ)
Breaker Type
Frame Size
WPF-08
800A
WPF-16 Ž
1600A
WPS-20 
2000A
WPS-32 
3200A
WPS-40 
4000A
WPS-50 
5000A
* These fuse sizes are also available as "Welder Limiters."
ΠClass L fuses less than 800A are not UL or CSA listed. Use Class J fuses for 600A and below. The maximum fuse rating is the largest fuse that tests show will result in proper perfor-
mance of the breaker and fuse in combination under short-circuit conditions. Only Gould- Shawmut fuses should be used for proper coordination.
 Fuses are mounted in a separate roll-out element (fuses shipped as "XS" material).
Ž Integrally fused 1600A frame breakers (WPF-16) equipped with 2500A fuses can be furnished with rating plugs from 300-1600A. Breakers equipped with 2500A fuses
cannot be modified to accept lower rated fuses. WPF-16 breakers equipped with 2000A and lower fuses cannot be upgraded to 2500A fuses. The maximum trip rating
for a WPF-16 breaker is 1200A when furnished with other than 2500A fuses (see chart for min-max fuse rating for each rating plug value). 2500A fuses preclude the use of
shutters in the breaker cubicle.
12
Available Rating Plugs
60 Π, 80, 100, 125, 150
150 Π, 200, 225, 250, 300, 400
300 Π, 400, 450 Π, 500, 600, 700, 800
600 Π, 800, 1000, 1100 Π, 1200, 1600
750 Π, 800 Π, 1000, 1200, 1500 Π, 1600, 2000
1200, 1600, 2400, 3200
1600, 2000, 2500, 3000, 3600 Π, 4000
3200 Œ , 4000 Œ , 5000 Œ
Sensor Rating
150A
400A
800A
800A
1600A
2000A
3200A
4000A
5000A
Table 12.1 WavePro Breaker Interrupting Ratings
Rated AC
Voltage,
Nominal
Breaker
(max)
Type
WPS-08
WPH-08
WPX-08
600
WPS-16
WPH-16
(635)
WPS-20
WPS-32
WPH-32
WPX-32
WPS-40
WPX-40
WPS-50
WPX-50
WPS-08
WPH-08
WPX-08
480
WPS-16
WPH-16
(508)
WPS-20
WPS-32
WPH-32
WPX-32
WPS-40
WPX-40
WPS-50
WPX-50
WPS-08
WPH-08
WPX-08
240
WPS-16
WPH-16
(254)
WPS-20
WPS-32
WPH-32
WPX-32
WPS-40
WPX-40
WPS-50
WPX-50
Rating Plug
Below 150A
150A
225A
300A
400A
400 / 450 / 500 / 600 / 800* / 1000* / 1200* / 1600*A
600A
600 / 800* / 1000* / 1200* / 1600*A
700A
800A
450 / 500 / 600 / 800* / 1000* / 1200* / 1600* / 2000* / 2500A Ž
400A and below
500 / 600 / 800* / 1000* / 1200* / 1600* / 2000* / 2500A Ž
500A
600 / 800* / 1000* / 1200* / 1600* / 2000* / 2500A Ž
600A
800* / 1000* / 1200* / 1600* / 2000* / 2500A Ž
700A
800A
1000* / 1200* / 1600* / 2000* / 2500A Ž
1000A
1200A
1600A
2000A and below
3200A and below
4000A and below
5000A and below
Short-Circuit Ratings
RMS Symmetrical kA
With
Frame
Short-Time Instantaneous Instantaneous
Size (amps) Withstand Trip
800
30
30
800
42
42
800
50
50
1600
42
42
1600
65
65
2000
65
65
3200
65
65
3200
85
85
3200
85
85
4000
85
85
4000
85
85
5000
85
85
5000
85
85
800
30
30
800
42
42
800
65
65
1600
50
50
1600
65
65
2000
65
65
3200
65
65
3200
85
85
3200
100
100
4000
85
85
4000
100
100
5000
85
85
5000
100
100
800
30
42
800
42
50
800
65
65
1600
50
65
1600
65
65
2000
65
65
3200
65
85
3200
85
130
3200
100
130
4000
85
130
4000
100
130
5000
85
130
5000
100
130
Gould-Shawmut Fuse Range Œ
300 / 350 / 400 / 450 / 500 / 600 /
800* / 1000* / 1200* / 1600*A
800* / 1000* / 1200* / 1600*A
1000* / 1200* / 1600*A
1600* / 2000* / 2500A Ž
2500A Ž
2000 / 2500A
2000 / 2500 / 3000 / 4000A
2000 / 2500 / 3000 / 4000 / 5000A
Without
Trip
30
42
50
42
65
65
65
85
85
85
85
85
85
30
42
65
50
65
65
65
85
100
85
100
85
100
30
42
65
50
65
65
65
85
100
85
100
85
100