Table 3.4 Recommended Cable Sizes - Mitsubishi Electric 9900CX SERIES Owner Technical Manual

Inclusive parallel operation system application
Table of Contents

Advertisement

kVA
Input
Output
Capacity
Voltage
Voltage
1050kVA
480V
480V
1400kVA
480V
480V
1750kVA
480V
480V
2100kVA
480V
480V
*1 – Use 75 degree C copper wire.
*2 - The cables must be selected to be equal or larger to the sizes listed in the table.
*3 - Voltage drop across power cables not to exceed 2% of nominal source voltage.
*4 - Allowable ampere-capacities based on copper conductors with 75 degree C. insulation at ambient temperature of 40 degree C.
Recommended Hardware
Table 3.5
UPS Capacity
Bolt size
1050kVA
M12 x 40mm
1400kVA
M12 x 40mm
1750kVA
M12 x 40mm
2100kVA
M12 x 40mm
OWNERS / TECHNICAL MANUAL

Table 3.4 Recommended Cable Sizes

Input Side
Cable
Torque
Size
in. lbs
347 - 469
6 x 500MCM
6 x 500MCM
in. lbs
347 - 469
6 x 500MCM
6 x 500MCM
in. lbs
347 - 469
7 x 500MCM
7 x 500MCM
in. lbs
347 - 469
9 x 500MCM
9 x 500MCM
in. lbs
Split
Flat washer
lockwasher
size
size
M12
M12
M12
M12
M12
M12
M12
M12
MITSUBISHI ELECTRIC 9900CX SERIES UPS
9900CX SERIES UPS
Output Side
Cable
Torque
Cable
Size
in. lbs
Size
347 - 469
6 x 500MCM
in. lbs
347 - 469
6 x 500MCM
in. lbs
347 - 469
7 x 500MCM
in. lbs
347 - 469
9 x 500MCM
in. lbs
Nut size
M12
M12
M12
M12
Page Number:
3-4
Bypass Side
DC Input Side
Torque
Cable
in. lbs
Size
347 - 469
10 x 500MCM
in. lbs
347 - 469
11 x 500MCM
in. lbs
347 - 469
12 x 500MCM
in. lbs
347 - 469
14 x 500MCM
in. lbs
Torque
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs
347 - 469
in. lbs