Siemens SITRANS LUT400 Manual page 37

Communications (hart)
Hide thumbs Also See for SITRANS LUT400:
Table of Contents

Advertisement

To set Service/Calibration schedules:
1)
Open the menu Device – Maintenance, and click on the Service/Calibration
Schedule tab.
2)
Modify desired values, and if desired, set reminders for either or both of Reminder 1
(Required)/Reminder 2 (Demanded).
3)
Click on Write.
4)
Click on Read, to see the effects of your modification.
5)
Click on Service/Calibration Performed to reset the schedule.
Wear
Reports the number of days the device has been operating, and the number of times it
has been powered up.
Open the menu Device – Wear to view:
Powered-on Time
Power-on Resets
Flow Log
Set flow logging mode, with intervals and setpoints for standard and rapid flow rates.
Open the menu Device – Flow Log to view:
Flow Log Mode
Standard Flow Log Interval
Standard Flow Log Setpoint
Rapid Flow Log Interval
Rapid Flow Log Setpoint
Totalizers
Two different totalizers can be setup: OCM Flow Totalizer, Pumped Volume Totalizer.
Open the menu Device – Totalizers to view:
OCM Flow Totalizer
Totalizer Decimal Position
Totalizer Multiplier
Low Flow Cutoff
Pumped Volume Totalizer
Totalizer Decimal Position
Totalizer Multiplier
Set Pump Runtimes
Set runtime for each pump.
Open the menu Device – Set Pump Runtimes to view:
Run Time Relay 2
Run Time Relay 3
A5E33701270
COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL
Page 33