Advertisement

Features & Benefits
Transmit 12 RTD-based temperature measurements and a single contact status
up to 500 meters using inexpensive fiber-optic cable with the SEL-2600 RTD
Module. The SEL-2600 connects directly to the SEL-701 Motor Relay using fiber-
optic connectors built into each device and also connects to the SEL-2030 Commu-
nications Processor using a single SEL-2800 Fiber-Optic Transceiver. The fiber-
optic link eliminates expensive cable pulls and provides electrical noise immunity
and ground isolation.
Measure up to 12 RTD temperatures plus one contact input with
zero settings.
LEDs indicate device status, transmit status, and contact
input status.
Power from 120 Vac or 240 Vac.
Operates in extreme ambient temperatures from – 40º to +85º C .
Date Code 20000525
SEL-2600 RTD Module
Instruction Manual
100-ohm platinum
100-ohm nickel
120-ohm nickel
10-ohm copper
SEL-2600 RTD Module

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SEL-2600 and is the answer not in the manual?

Questions and answers

Summary of Contents for Sel SEL-2600

  • Page 1 Features & Benefits Transmit 12 RTD-based temperature measurements and a single contact status up to 500 meters using inexpensive fiber-optic cable with the SEL-2600 RTD Module. The SEL-2600 connects directly to the SEL-701 Motor Relay using fiber- optic connectors built into each device and also connects to the SEL-2030 Commu- nications Processor using a single SEL-2800 Fiber-Optic Transceiver.
  • Page 2: Initial Checkout

    Figure 1 on page 4. Set the relay as directed in SEL-701 Motor Relay Application on page 4. NOTE: The SEL-701 front panel may display “RTD Failure” if the correct RTDs are not yet connected. The SEL-701 METER T report displays the RTD temperature as “Comm Fail”...
  • Page 3: Installation

    Ground the SEL-2600 by connecting Terminal 26 to an appropriate electrical ground. Step 5. Connect as many as 12 RTDs to the SEL-2600 terminal blocks (see Figure 5 on page 13). Step 6. Record the type and location of each RTD in Table 1 on page 4.
  • Page 4: Sel-701 Motor Relay Application

    SEL-701 Motor Relay accurately tracks the heating effects of overloads and unbalance current. Combining the SEL-2600 and the SEL-701 Motor Relay enhances this list of protection features by adding remote RTD-based thermal protection. Fiber-Optic Ports (built into SEL-2600 &...
  • Page 5 Set the SEL-701 Motor Relay to accept the RTD temperature data packets (see Data Packet Definition on page 11) sent by the SEL-2600. You can use any of the following three methods to enter the settings. Relay front-panel menus: Set Relay\Relay Elements\RTD CONFIGURATION.
  • Page 6: Receive Temperature Data

    The next few pages describe how to configure the SEL-2030 to perform the four automated steps shown above. It is assumed that the SEL-2600 is connected to Serial Port 4 of the SEL-2030. Refer to the SEL-2030 Communications Processor Reference Manual and the SEL-2030 Communications Processor User’s Guide for...
  • Page 7 Mover Figure 3 Generator Protection with the SEL-300G Relay. SCADA PC/HMI SEL-2030 Communications Processor SEL-2800 EIA-232 Fiber-Optic Transceiver SEL-2600 SEL-587/387 Relay RTD Module Transformer Figure 4 Transformer Protection with the SEL-587 or SEL-387 Relay. Date Code 20000525 SEL-2600 RTD Module...
  • Page 8: Store Temperature Data In Sel-2030 Memory

    (see Table 3 on page 11) into the reserved USER data region at the addresses shown in Table 2 on page 9. The SEL-2600 data packet includes temperature information for each of the four types of RTDs. To access the correct temperature, use the memory map loca- tion associated with the correct RTD type.
  • Page 9 Line 4: Copies the sign bit (Bit 15) of 034h into Bit 0 of 035h. Line 5: Clears Bit 0 of 35h if RTD is shorted. Line 6: Clears Bit 0 of 35h if RTD is open. Table 2 SEL-2030 Communications Processor Memory Map Table 2 SEL-2030 Communications Processor Memory Map Address (hex)
  • Page 10: Issue Control Commands To Relay

    The following example settings assume the relay is connected to SEL-2030 Serial Port 10, and the SEL-2600 is connected to Serial Port 4. SET L 10 SBR1 = 4:USER:35h:0 #If above threshold open breaker 1...
  • Page 11: Data Packet Definition

    Data Packet Definition Data Packet Definition The SEL-2600 RTD Module sends a binary data packet every 0.5 seconds. The packet contains data for all four types of supported RTDs so no settings are required in the SEL-2600 (patent pending). Using the SEL-2800 Fiber-Optic Transceiver, any EIA-232 device can be configured to understand the binary data packet con- tents shown in Table 3.
  • Page 12: Sel-2600 Guideform Specifications

    SEL-2600 Guideform Specifications SEL-2600 RTD Module Data Packet Definition (Continued) Table 3 Data Data Value Size Description Four words are sent for each of the 12 inputs. Use only the appropriate temperature for the type of RTD connected to each input.
  • Page 13: Wiring Diagram

    — — — — — — LEDs IN— ENABLE Speed switch or other contact INPUT +120 or 240 Vac 120 Vac Neutral 240 Vac Neutral Figure 5 SEL-2600 Wiring Diagram. N=Neutral, N/C=No Connection, RTN=Return. Date Code 20000525 SEL-2600 RTD Module...
  • Page 14: Mechanical Diagram

    Mechanical Diagram 1.750" (44.45 mm) Top View 9.500" 8.515" 9.000" (241.30 mm) (216.28 mm) (228.60 mm) φ0.203" (φ5.16 mm) 4.418" (112.22 mm) 0.620" (15.75 mm) 2.060" End View (52.32 mm) Figure 6 SEL-2600 Mechanical Diagram. SEL-2600 RTD Module Date Code 20000525...
  • Page 15: Specifications

    Cold: IEC 60068-2-1: 1990, of UL-508; CSA C22.2, N.14 for Industrial Test Ad; Control Equipment. – 16 hr @ 40°C CE: CE Mark. Dry Heat: IEC 68-2-2: 1974, Test Bd; 16 hr @ +85°C Date Code 20000525 SEL-2600 RTD Module...
  • Page 16 Notes SCHWEITZER ENGINEERING LABORATORIES Schweitzer Engineering Laboratories, SEL , and are regis- OGIC 2350 NE Hopkins Court • Pullman, WA 99163-5603 USA tered trademarks of Schweitzer Engineering Laboratories. All brand Phone: (509) 332-1890 • Fax: (509) 332-7990 or product names appearing in this document are the trademark or Internet: www.selinc.com •...

Table of Contents