SEL-2243 Power Coupler
®
Every SEL Axion
node requires at least one SEL-2243 Power Coupler module. The SEL-2243 serves two purposes in
an Axion system:
1.
It is the power supply for all modules installed in the node, and;
2.
It provides two dedicated EtherCAT

Front Panel

i5398d
Figure 1 SEL-2243 Front Panel With RJ45 Connectors
Power Supply Operation
One SEL-2243 has sufficient power capacity to accom-
modate an entire Axion node. The terminal strip at the
bottom of the unit, as seen in Figure 1, is the connection
point for incoming power. All Axion modules have a
55-position IEC C-style connector that provides a com-
munications and power interface to the backplane. The
SEL-2243 provides power to the node via the backplane
connector.
Schweitzer Engineering Laboratories, Inc.
®
ports so that multiple Axion nodes can operate together.
The power coupler module uses the same power supply
design that you would find in SEL protective relays. The
Axion provides test-proven superior performance and
availability, while also allowing for redundant power
couplers in a node for applications that need these. If you
install two power couplers in a node, both modules
actively share load and provide the necessary power for
node functions. If one SEL-2243 becomes unavailable,
there is zero switching delay or power loss to the node.
EtherCAT Operation
Each SEL-2243 provides two dedicated ports for Ether-
CAT networks. The ports will either be standard
10/100BASE-T or optional 100BASE-FX Ethernet ports.
EtherCAT is a real-time fieldbus protocol (see
Appendix E in the
Instruction Manual) that we can use to connect an RTAC
to I/O modules in an Axion system. If the installation has
only one node, then the backplane transmits EtherCAT
messages. Alternatively, if you use an SEL-3530 RTAC,
or if you need more I/O than will fit in a node, then the
ports on a power coupler module provide a mechanism
for extending the EtherCAT network through the use of
dedicated Ethernet wiring. Refer to EtherCAT in
Section 2: Communications in the
i5695b
SEL-5033 Instruction Manual to learn more about con-
figuring a network.
If an Axion node contains two SEL-2243 modules, then
the EtherCAT ports in both power couplers will operate
normally even if one power supply becomes unavailable.
The remaining power supply will serve as the source for
all I/O modules and communications needs.
SEL
RTAC SEL-5033
AC
ERATOR
SEL
AC
ERATOR
SEL-2243 Data Sheet
RTAC

Advertisement

loading
Need help?

Need help?

Do you have a question about the SEL-2243 and is the answer not in the manual?

Questions and answers

Summary of Contents for Sel SEL-2243

  • Page 1: Front Panel

    SEL-2243 Power Coupler ® Every SEL Axion node requires at least one SEL-2243 Power Coupler module. The SEL-2243 serves two purposes in an Axion system: It is the power supply for all modules installed in the node, and; ® It provides two dedicated EtherCAT ports so that multiple Axion nodes can operate together.
  • Page 2 (refer to Figure 4). Finally, Each SEL-2242 chassis/backplane has ten slots, labeled press the module firmly into the chassis and tighten the A through J. Only slots A, B, and C support the SEL-2243 chassis retaining screw. Power Coupler module.
  • Page 3: Specifications

    The green LED labeled POWER on the SEL-2243 will illu- SEL-2243 includes 10/100BASE-T 100BASE-FX Ethernet ports dedicated for EtherCAT minate if incoming power is present and the power sup- ply is operating normally. The LEDs labeled ENABLED protocol. Use a standard RJ45 connector for a copper port and an LC connector for a fiber-optic port to connect and ALARM are related to EtherCAT network operation.
  • Page 4 All brand or product names appearing in this document are the trademark or registered trademark of their respective holders. No SEL trademarks may be used without written Tel: +1.509.332.1890 • Fax: +1.509.332.7990 permission. SEL products appearing in this document may be covered by U.S. and Foreign selinc.com • info@selinc.com patents.