In-Tank Leak Tests
Press ENTER to confirm your choice:
AUTOMATIC
PRESS <STEP> TO CONTINUE
If you are setting up the test for All Tanks, the setup is complete. Press FUNCTION to exit.
If you are setting up the test for Single Tanks, the setup is complete for the tank you are setting up. Press STEP
and press TANK/SENSOR to choose the next tank. Return to the beginning of the section "Leak Test Frequency"
on page 8-2 and repeat the procedure for the next tank.
CSLD - OPTION
NOTE: The CSLD option appears only when the tank is equipped with a 0.1 gph (0.38 lph) Mag probe, and the
system has the CSLD software module key installed.
If necessary, press STEP until you see the message:
TEST ALL TANK:
ON DATE
To run the test using the CSLD frequency option, press CHANGE repeatedly until you see CSLD on the display.
Press ENTER to confirm your choice:
CSLD
PRESS <STEP> TO CONTINUE
Press STEP to display the message:
CSLD Pd: ALL TANKS
Pd = 95%
You can set the Pd (Probability of Detection) to 95% or 99%. To accept the 95% value, press STEP. (The system
displays the CLIMATE FACTOR message.) If "Custom" appears in this field, a special value has been entered
remotely. Do not change the selection from Custom. This selection is used primarily for European operations.
To change the value to 99%, press CHANGE, then press ENTER to confirm your choice:
Pd = 99%
PRESS <STEP> TO CONTINUE
Press STEP to display the message:
CLIMATE FACTOR: ALL TANKS
MODERATE
The default is Moderate and the other choice is Extreme.
Climate Factor - set to Moderate
Press STEP to display the message:
TEST ALL TANKS
CSLD
If you are setting up the CSLD test frequency for All Tanks, the setup is complete. Press FUNCTION to exit.
8-5
Leak Test Frequency