ABB ABILITY SSC600 Product Manual page 40

Smart substation control and protection for electrical systems
Hide thumbs Also See for ABILITY SSC600:
Table of Contents

Advertisement

Product Guide
SSC600
Product version: 1.0
29.3 Advanced Feeder Application Package
Advanced Feeder Application Package can be selected with order
code Digit 5, and it can be selected for 5,10,15 or 20 feeders.
The size of the package impacts the number of available function
instances. The content of the package is described in the table
below.
Table 122. Protection
Function Name
Admittance based earth-fault protection
Multi-frequency admittance-based earth-
fault protection
Wattmetric based earth-fault protection
Transient / intermittent earth-fault protection INTRPTEF
Fault locator
Directional reactive power under voltage
protection
Low voltage ride through protection
29.4 Transformer Application Package
Transformer Application Package can be selected with order code
Digit 7, and it can be selected for 2 or 4 feeders. The size of the
package impacts the number of available function instances. The
content of the package is described in the table below.
Table 123. Protection
Function Name
Three-phase thermal overload protection
for power transformers, two time constants
Stabilized and instantaneous differential
protection for 2-winding transformers
Numerical stabilized low impedance
restricted earth-fault protection
Table 124. Control
Function Name
Tap changer position indication
40
Number of Instances
IEC 61850 Name
5 Feeders
EFPADM
15
MFADPSDE
15
WPWDE
15
5
SCEFRFLO
5
DQPTUV
5
LVRTPTUV
15
Number of Instances
IEC 61850 Name
2 Feeders
T2PTTR
2
TR2PTDF
2
LREFPNDF
2
Number of Instances
IEC 61850 Name
2 Feeders 4 Feeders
TPOSYLTC
2
10 Feeders
15 Feeders
20 Feeders
30
45
60
30
45
60
30
45
60
10
15
20
10
15
20
10
15
20
30
45
60
4 Feeders
4
4
4
4
1MRS758725
ABB

Advertisement

Table of Contents
loading

Table of Contents