24. Tools

The protection device is delivered as a preconfigured unit. The de-
fault parameter setting values can be changed from the frontpanel
user interface (local HMI), the Web browser based user interface
(Web HMI) or Protection and Control IED Manager PCM600 in
combination with the IED-specific connectivity package.
PCM600 offers extensive IED configuration functions. For exam-
ple, depending on the protection IED, the IED signals, application,
graphical display and single-line diagram, and IEC 61850 com-
munication, including horizontal GOOSE communication, can be
modified with PCM600.
When the Web HMI is used, the protection device can be ac-
cessed either locally or remotely using a Web browser (Internet
Explorer). The Web HMI functionality can be limited to read-only
access. Local control from Web HMI is possible only when the
device is accessed from the local Web HMI Ethernet port.
Table 101. Tools
Description
PCM600
Web browser
SSC600 Connectivity Package
Table 102. Supported functions
Function
Device parameter setting
Saving of device parameter settings in the device
Signal monitoring
Disturbance recorder handling
Alarm LED viewing
Access control management
device signal configuration (Signal Matrix)
Saving of device parameter settings in the tool
Disturbance record analysis
XRIO parameter export/import
Graphical display configuration
Application configuration
IEC 61850 communication configuration, GOOSE (com-
munication configuration)
Phasor diagram viewing
Event viewing
Saving of event data on the user's PC
Online monitoring
• = Supported

25. Cyber security

The device supports role based user authentication and authori-
zation. It can store 2048 audit trail events to a nonvolatile memory.
The non-volatile memory is based on a memory type which does
not need battery backup or regular component exchange to
maintain the memory storage. FTP and Web HMI use TLS encryp-
tion with a minimum of 128 bit key length protecting the data in
transit. In this case the used communication protocols are FTPS
and HTTPS. All rear communication ports and optional protocol
32
Web HMI
-
-
-
-
-
-
-
Version
2.9 or later
Internet Explorer 8.0, 9.0, 10.0 and 11.0
1.0 or later
PCM600
-
1MRS758725
ABB

Advertisement

Table of Contents
loading

Table of Contents