Characteristic
Suppression of harmonics
Table 95. Sequence voltage measurement (VSMSQI)
Characteristic
Operation accuracy
Suppression of harmonics
Table 96. Three-phase power and energy measurement (PEMMXU)
Characteristic
Operation accuracy
Suppression of harmonics
Table 97. Frequency measurement (FMMXU)
Characteristic
Operation accuracy

21. Other functions

Table 98. Pulse timer (PTGAPC)
Characteristic
Operation accuracy
Table 99. Time delay off (8 pcs) (TOFGAPC)
Characteristic
Operation accuracy
Table 100. Time delay on (8 pcs) (TONGAPC)
Characteristic
Operation accuracy
67 |PF| >0.5 which equals |cos φ | >0.5
68 |PF| <0.86 which equals |sin φ | >0.5
30
Value
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,...
RMS: No suppression
Value
Depending on the frequency of the voltage measured: fn ±2 Hz At voltages in
range 0.01...1.15 × Un
±1.0% or ±0.002 × Un
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,...
Value
At all three currents in range 0.10...1.20 × In
At all three voltages in range 0.50...1.15 × Un
At the frequency fn ±1 Hz
±1.5% for apparent power S
±1.5% for active power P and active energy
±1.5% for reactive power Q and reactive energy
±0.015 for power factor
DFT: -50 dB at f = n × fn, where n = 2, 3, 4, 5,...
Value
±5 mHz
(in measurement range 35...75 Hz)
Value
±1.0% of the set value or ±20 ms
Value
±1.0% of the set value or ±20 ms
Value
±1.0% of the set value or ±20 ms