Area Of Application - Siemens 3TM Operating Instructions Manual

1-pole vacuum contactor 4.15 kv - 6.9 kv
Hide thumbs Also See for 3TM:
Table of Contents

Advertisement

General information
Applications
Function
Intended use
IEC/DIN EN 62271-1
IEC/DIN EN 62271-106
IEC/DIN EN 62271-200
GB/T14808
ANSI
CSA C22.2 No. 253-09
NMX-J-564/106-ANCE
IEC 61000-4
IEC 61000-6
IEC 60068
10

Area of application

Vacuum contactors 3TM are 1-pole switching devices with an electromagnetic op-
erating mechanism for high switching capacity and a rated voltage range from
4.15 kV to 6.9 kV (single-phase, rigidly earthed star point).
Vacuum contactors 3TM comply with the protection class IP00 (stationary, weather-
protected operation) as per EN 60529 and can be used
with circuit breakers and fuses,
for ambient temperatures from -40 °C to +70 °C,
at various altitudes ranging from -1250 m to 5000 m ASL,
for high mechanical vibrations or
for use in seismic zones,
on ships below deck,
on open pit or mining equipment,
in stationary or moving rail operation.
The technical data are affected by ambient conditions, installation position, and in-
stallation volume.
Operational currents and overload currents are switched by the vacuum contactor.
3TM vacuum contactors operate in continuous, periodic, and short-term operation.
Suitable for high frequency of operation and unlimited on-time.
Vacuum contactors 3TM are suitable for switching any type of alternating current cir-
cuits under normal operating conditions, such as:
Motors
Transformers
Resistor consumers
Neutral earthing
The vacuum contactor can be mounted:
as a fixed installation (with busbars or cables with cable lugs),
on a withdrawable part, or
on a carriage.
Standards
Vacuum contactors 3TM comply with the following standards:
High-voltage switchgear and controlgear – Part 1: Common specifications
High-voltage switchgear and controlgear – Part 106: Contactors and controllers
High-voltage switchgear and controlgear – Part 200: AC metal-enclosed switchgear
and controlgear
High voltage alternating current contactors and contactor-based motor-starters
American National Standard (ANSI), harmonized ANCE, CSA, and UL Standard for
medium-voltage ac contactors, controllers, and control centres
Medium-Voltage AC Contactors, Controllers, and Control Centers
Medium-Voltage AC Contactors, Controllers, and Control Centers
Electromagnetic compatibility (EMC)
Parasitic x-ray emittance and interference voltage
Environmental test procedures
9229 0098 176 0-
2019-01-09

Hide quick links:

Advertisement

Table of Contents
loading