Controller Settings/Outputs - ABB C1900 Installation Manual

Circular chart recorder and recorder/controller, modbus (rtu) communications option
Hide thumbs Also See for C1900:
Table of Contents

Advertisement

7.3 Controller Settings/Outputs

Register Number
Read/Write
051
052
053
054
055
056
057
058
059
060
061
062
063
064
065
066
067
068
069
070
071
072
073
074
075
076
077
078
079
080
081
082
083
084
085
086
087
088
089
090
Description
Controller Settings/Outputs
Channel 1
R
Process Variable 1
R/W
Control Set Point
R/W
Control Output (write in manual mode)
R
Position Feedback 1
R
Position Feedback 1 Failure State
R/W
On/Off Hysteresis Value
R/W
Cycle-Time Heat Control
R/W
Proportional Band (Heat) Control
R/W
Integral Value (Heat) Control
R/W
Manual Reset (Heat) Control
R/W
Derivative Action
R/W
Approach Band
R/W
Heat Output (write manual mode only)
R/W
Cool Output (write manual mode only)
R/W
Proportional Band Cool Control
R/W
Integral Value Cool Control
R/W
Manual Reset Cool Control
R/W
Cycle-Time Cool Control
R/W
Crossover Band
R/W
Transition Band
Controller Settings/Outputs
Channel 2
R
Process Variable 2
R/W
Control Set Point
R/W
Control Output (write in manual mode)
R
Position Feedback 2
R
Position Feedback 2 Failure State
R/W
On/Off Hysteresis Value
R/W
Cycle-Time Heat Control
R/W
Proportional Band (Heat) Control
R/W
Integral Value (Heat) Control
R/W
Manual Reset (Heat) Control
R/W
Derivative Action
R/W
Approach Band
RW
Heat Output (write manual mode only)
RW
Cool Output (write manual mode only)
R/W
Proportional Band Cool Control
R/W
Integral Value Cool Control
R/W
Manual Reset Cool Control
R/W
Cycle-Time Cool Control
R/W
Crossover Band
R/W
Transition Band
7 MODBUS REGISTERS...
Response/Entry
–9999 to +9999
–9999 to +9999
0 to 1000 Representing (0.0.to 100.0%)
0 to 1000 Representing (0.0.to 100.0%)
0 = Input Active
1 = Input Failed
2 = A to D Failed
3 = Input and A to D Failed
0 to 1000 Representing (0.0.to 100.0%)
10 to 3000 (1.0 to 300.0 Seconds)
1 to 9999 (0.1 to 999.9%)
0 = OFF, 1 to 7200 Seconds
0 to 1000 (0.0 to 100.0%)
1 to 9999 (0.1 to 999.9 Seconds)
1 to 30 (0.1 to 3.0)
0 to 1000 (0.0 to 100.0%)
0 to 1000 (0.0 to 100.0%)
1 to 9999 (0.1 to 999.9%)
0 = OFF, 1 to 7200 Seconds
0 to 1000 (0.0 to 100.0%)
10 to 3000 (1.0 to 300.0 Seconds)
0 to 1000 (0.0 to 100.0%)
0 to 1000 (0.0 to 100.0%)
–9999 to +9999
–9999 to +9999
0 to 1000 Representing (0.0.to 100.0%)
0 to 1000 Representing (0.0.to 100.0%)
0 = Input Active
1 = Input Failed
2 = A to D Failed
3 = Input and A to D Failed
0 to 1000 Representing (0.0.to 100.0%)
10 to 3000 (1.0 to 300.0 Seconds)
1 to 9999 (0.1 to 999.9%)
0 = OFF, 1 to 7200 Seconds
0 to 1000 (0.0 to 100.0%)
1 to 9999 (0.1 to 999.9 Seconds)
1 to 30 (0.1 to 3.0)
0 to 1000 (0.0 to 100.0%)
0 to 1000 (0.0 to 100.0%)
1 to 9999 (0.1 to 999.9%)
0 = OFF, 1 to 7200 Seconds
0 to 1000 (0.0 to 100.0%)
10 to 3000 (1.0 to 300.0 Seconds)
0 to 1000 (0.0 to 100.0%)
0 to 1000 (0.0 to 100.0%)
17

Advertisement

Table of Contents
loading

Table of Contents