From the Program Change screen, selecting 7=SYS-
TEM (General System Functions) displays the
System Function screen. The sample screen to the
right shows a typical System Function screen. The
following details each item on the System Function
screen:
SIL INH (Silence Inhibit) may be set from 0 to 300
seconds.
AUTO (Auto Silence) may be set from 600 to 900 seconds, or to zero (none).
VERIFY (Alarm Verification time) may be set from 0 to 30 seconds (for systems with Software Release 1.2).
Verification times of 0 to 60 seconds were permitted in systems with Software Releases 1.0 and 1.1 only).
USA TIME may be changed to EUR TIME with the up/down cursor keys. The default is USA TIME.
Selecting EUR Time does the following: changes to 24-hour time, places day before month, provides FAULT
instead of TROUBL, and ISOLAT instead of DISABL in the display status field.
ANNUN=ACS(1+2) indicates two ACS type annunciators. ANNUN may be changed to ANNUN=ACS
ADDR 1 for a single ACS annunciator, to ANNUN=LCD-80(T) for use with an LCD-80 in terminal mode, to
ANNUN= UDACT for use with a UDACT Digital Communicator, or to ANNUN=NON SUPV for no annun-
ciator.
LocT may be selected meaning that there is a local CRT terminal in the same room as the control panel that is
allowed to Acknowledge, Silence, Drill and Reset the control panel. It may also be set to LocM (local monitor
only) or RemM (remote terminal status monitor only). The default setting is RemM (refer to Appendix I).
BLINK=Y (device LED blink) may be changed to BLINK=N (no blink) using the up/down cursor keys.
Note: When BLINK=N, a detector only blinks when the detector is tested (every three to four hours) but does
not blink each time it is polled.
ST=4 (Style four communications loop wiring) may be changed to ST=6 (Style 6 loop wiring).
AVPS=N (AVPS-24/AVPS-24E not installed) may be changed to AVPS=Y (AVPS-24/AVPS-24E is installed).
Refer to Appendix J for detailed information.
An upload/download of the control panel may be done at any time by connecting a personal computer to the
EIA-232 port and running the off-line programming routine. Refer to the PK-200 Off Line Programming Utility
manual for more information.
From the Program Change screen, selecting 8=CHECK directs the control panel to check the control program
as follows:
•
Search for output points that are mapped to a zone with no inputs mapped to it.
•
Search for input points that are mapped to a zone with no output points mapped to it (including Z00 outputs).
•
Search to see if releasing zones (91, 92, 93, and 94) have an input device but no RELEASE CKT; or have a
RELEASE CKT but no input device mapped to them.
Note: If multiple devices fail the check, use the up/down keys to step through the devices. To correct any errors
detected by the Check routing, return to point programming and correct the program errors.
56
S I L @ I N H = 0 6 0 @ A U T O = 6 0 0
V E R I F Y = 3 0 @ @ @ U S A @ T I M E
A N N U N = A C S ( 1 + 2 ) @ @ L o c T
B L I N K = Y @ S T = 4 @ A V P S = N
AFP-200 Instruction
PN 15511:F2
10/11/99