EMC Emissions
Radiated, Conducted
EMC Immunity
Generic Immunity
Industrial PLC Immunity
ITE Immunity
Electrostatic Discharge
RF Susceptibility
Fast Transient Burst
Surge Withstand
Conducted RF
Damped Oscillatory Wave
Installation Conditions:
•
USB, Ethernet, Serial, and VGA cables are shielded.
•
Serial cable limited to < 30 m (98 ft).
•
USB and VGA ports are intended as maintenance only ports.
†
EN 61000-4-x series of tests are technically equivalent to the IEC 61000-4-x series.
42
GFK-2898B
For public disclosure
EMC Standards
The RXi Display complies with the EMC test levels identified in the following table.
Standard
Conditions
Industrial Scientific and Medical Equipment (Group 1, Class A)
CISPR 11 / EN 55011
CISPR 22 / EN 55022 Information Technology Equipment (Class A)
Title 47 – Telecommunications, Radio Frequency Devices (Class A)
47 CFR 15
Information Technology Equipment (ITE) – Limits and methods of
ICES-003
measurement (Class A)
EN 61000-6-4
Generic Standards – Emission Standard for Industrial Environment
Standard
Minimum Required Test Level
EN 61000-6-2
Industrial environments
EN 61131-2
Zone B
EN 55024 / CISPR 24
EN 61000-4-2
†
±8.0 kV Air, ±4.0 kV contact
10 V
EN 61000-4-3
†
3 V
rms
1 V
rms
±2.0 kV dc input, ±1.0 kV signal
EN 61000-4-4
†
±0.5 kV dc input (Line-Line and Line-Earth)
EN 61000-4-5
†
±1.0 kV signal (Line-Earth)
10 V
EN 61000-4-6
†
±2.5 kV dc input (Line-Line and Line-Earth)
EN 61000-4-18
†
±2.5 kV signal (Line-Earth)
/m, 0.8 to 1.0 GHz
rms
/m, 1.0 to 2.0 GHz
/m, 2.0 to 2.7 GHz
, 0.15 to 80.0 MHz
rms
–
PACSystems 19" RXi Display