Commissioning Modes; Overview Of Commissioning With The Bop Or Aop; Quick Commissioning - Siemens SED2 series Operating Instructions Manual

Variable speed drives
Hide thumbs Also See for SED2 series:
Table of Contents

Advertisement

Prerequisites:
. . . .
Note
46/126
Siemens Building Technologies
HVAC Products

5.4 Commissioning modes

5.4.1

Overview of commissioning with the BOP or AOP

Mechanical and electrical installation must be complete.
Setting the mains frequency
DIP switch 2: OFF = 50 Hz / ON = 60 Hz
Check prior to start
See section 5.2 checklist prior to switch-on.
Einschalten
Quick commissioning P0010=1
See section 5.4.2
Further commissioning via
P0004 (parameter filter) and P0003 access level
Refer to the parameter list for detailed information
on the
parameters.
* Factory setting: 50 Hz.
We recommend that you commission the VSD as shown in the diagram below.
However, experienced users may commission the equipment without the filter
functions of P0004.
5.4.2

Quick commissioning

To achieve a structured procedure, it is important to use parameter P0010 for
commissioning, and P0003 to select the number of parameters to be accessed.
Parameter P0010 allows you to select a group of parameters that can be used for quick
commissioning. These include parameters for the motor data and for the motor ramp-
up and ramp-down settings (ramp settings).
At the end of the quick commissioning procedure, select P3900. When set to 1, this
parameter performs the necessary motor calculations and sets all remaining
parameters (those not included under P0010 = 1) to the default values, including
P0010=0 (if P0010 is set to 1, the VSD cannot start). This process is only possible in
"quick commissioning" mode.
SED2 variable speed drives
Commissioning
*
CM1U5192en
01.2002