Summary of Contents for Mitsubishi Electric MELSEC FX2N-64CL-M

  • Page 1 MITSUBISHI ELECTRIC MELSEC FX Series Programmable Controllers User's Manual (Detailed Volume) -64CL-M CC-Link/LT Master Block 01 01 2003 INDUSTRIAL AUTOMATION MITSUBISHI ELECTRIC JY997D08501 Version A...
  • Page 2 • If the user is in any doubt about the operation or use of FX -64CL-M CC-Link/LT Master Block please consult the nearest Mitsubishi Electric distributor. • This manual is subject to change without notice.
  • Page 3 FX2N-64CL-M CC-Link/LT Master Block -64CL-M CC-Link/LT Master Block USER’S MANUAL (Detailed Volume) Manual number : JY997D08501 Manual revision : A Date : January 2003...
  • Page 4 FX2N-64CL-M CC-Link/LT Master Block...
  • Page 5 Mitsubishi users are always welcomed. This page has been designed for you, the reader, to fill in your comments and fax them back to us. We look forward to hearing from you. Fax numbers: Your name: ........... Mitsubishi Electric................. America (01) 847-478-2253 Your company: ..........
  • Page 6 FX2N-64CL-M CC-Link/LT Master Block...
  • Page 7 FX2N-64CL-M CC-Link/LT Master Block Safety guidelines for the User and Protection of the FX -64CL-M This manual provides information for the use of the FX -64CL-M. The manual has been written to be used by trained and competent personnel. The definition of such a person or persons is as follows;...
  • Page 8 FX2N-64CL-M CC-Link/LT Master Block • Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage that may arise as a result of the installation or use of this equipment. • All examples and diagrams shown in this manual are intended only as an aid to understanding the text, not to guarantee operation.
  • Page 9: Table Of Contents

    FX2N-64CL-M CC-Link/LT Master Block Table of Contents Safty guidelines..................v Generic Names and Abbreviations............1 1. Outline ....................1-1 1.1 Product Outline ....................1-1 1.2 Features ......................1-1 1.3 Name and assignment of each part ..............1-2 2. Specifications ..................2-1 2.1 General specifications ..................2-2 2.2 Network wiring specifications ................
  • Page 10 FX2N-64CL-M CC-Link/LT Master Block 8. Assignment of I/O Nos................8-1 8.1 Relationship between I/O No. and point mode ............ 8-1 8.2 Example of I/O No. assignment ................8-2 8.3 Automatic I/O No. assignment ................8-3 8.3.1 Automatic I/O No. assignment procedure ..............8-3 8.4 Specification of reserved station................
  • Page 11: Generic Names And Abbreviations

    FX2N-64CL-M CC-Link/LT Master Block Generic Names and Abbreviations Generic Names and Abbreviations The generic names and abbreviations shown below are used within explanation contained in this manual. Generic name/abbreviation Description -64CL-M CC-Link/LT Master block FX -64CL-M Station which controls the data link system. Master station One master station is required in one system.
  • Page 12 FX2N-64CL-M CC-Link/LT Master Block Generic Names and Abbreviations MEMO...
  • Page 13: Outline

    FX2N-64CL-M CC-Link/LT Master Block Outline 1 Outline Product Outline The CC-Link/LT master block FX -64CL-M can be connected to the FX Series PLC. The CC-Link/LT system can be constructed with an FX Series PLC as the master station. Features The FX -64CL-M has the following features: 1) Reduced wiring time The adoption of flat cabling for CC-Link/LT and special connector allow for reduced wiring...
  • Page 14: Name And Assignment Of Each Part

    FX2N-64CL-M CC-Link/LT Master Block Outline 1 Name and assignment of each part DIP switch for operation setting 2-φ4.5(0.18") mounting hole (M4 mounting screw) Status indicator LEDs TEST ONLINE CONFIG ONLINE 16pts. 4pts. B RATE -64CL-M Extension cable Extension connector connected to PLC connected to an extension block/unit or special block/unit of the PLC...
  • Page 15 FX2N-64CL-M CC-Link/LT Master Block Outline 1 Name Description <ONLINE mode> :Communication speed setting error occurred EEPROM read error (sum mismatch) occurred Flickering :Power supplied for communication is abnormal DIP switch for operation setting was changed during operation Extinguished :FX -64CL-M is operating normally <CONFIG mode>...
  • Page 16 FX2N-64CL-M CC-Link/LT Master Block Outline 1 Name Description Communication speed setting Communication speed 156 kbps B RATE 625 kbps 2.5 Mbps Setting disabled Point mode setting (Select the number of I/O points per station.) 3 16pts/4pts OFF:4-point mode (4 input points and 4 output points in each station) ON :16-point mode (16 input points and 16 output points in each station) Setting is disabled.
  • Page 17: Specifications

    FX2N-64CL-M CC-Link/LT Master Block Specifications 2 Specifications This section explains the specifications of the FX -64CL-M. DESIGN PRECAUTIONS When a remote I/O unit fails, outputs may randomly set ON or OFF, therefore, build an external monitoring circuit that will monitor any input signals that could cause a serious accident.
  • Page 18: General Specifications

    FX2N-64CL-M CC-Link/LT Master Block Specifications 2 General specifications Item Specification Operating temperature 0 to 55°C (32 to 131°F) Storage temperature -20 to 70°C (-4 to 158°F) Operating humidity 35 to 85%RH (Dew condensation should not be allowed.) Number of sweep Direct mounting times Frequency...
  • Page 19: Performance Specifications

    FX2N-64CL-M CC-Link/LT Master Block Specifications 2 Performance specifications Item Specification Series PLC (Section 4.3) Applicable PLC -CNV-IF is required when FX Series PLC is connected.) Series: Up to 4 Number of connectable master Series: Up to 8 blocks Series: Up to 3 Applicable point mode 4-point mode and 16-point mode (selectable by DIP switch) 4-point mode...
  • Page 20: Outside Dimensions

    FX2N-64CL-M CC-Link/LT Master Block Specifications 2 Outside Dimensions 4(0.16) 2-φ4.5(0.18) ERR. L RUN L ERR. POWER -64CL-M 43(1.70) 87(3.43) Unit: mm(inches)
  • Page 21: System Startup Procedure

    FX2N-64CL-M CC-Link/LT Master Block System Startup Procedure 3 System Startup Procedure Start up the CC-Link/LT system using the following procedure. Start Refer to Install the FX -64CL-M, remote I/O units and power adapter to the control panel and machine. Section 5. Connect the FX -64CL-M, remote I/O units and power adapter with the dedicated flat cables.
  • Page 22 FX2N-64CL-M CC-Link/LT Master Block System Startup Procedure 3 MEMO...
  • Page 23: System Configuration

    FX2N-64CL-M CC-Link/LT Master Block System Configuration 4 System Configuration This section explains the CC-Link/LT system configuration. DESIGN PRECAUTIONS When a remote I/O unit fails, outputs may randomly turn ON or OFF, therefore, build an external monitoring circuit that will protect from any input signals that could cause a serious accident.
  • Page 24: Total Configuration

    FX2N-64CL-M CC-Link/LT Master Block System Configuration 4 Total configuration This paragraph describes the system configuration and cautions for CC-Link/LT. Trunk length (branch line length not included) T branch PLC main unit T-branch interval connection Terminating Terminating Power Remote Remote resistor resistor adapter I/O station...
  • Page 25: Plc Connection

    FX2N-64CL-M CC-Link/LT Master Block System Configuration 4 PLC connection This paragraph explains which PLC series are connectable with the FX -64CL-M and cautions on the number of connectable FX -64CL-M. 4.2.1 Applicable PLC and number of connectable FX -64CL-M Series PLC Applicable PLC -CNV-IF is required when FX Series PLC is connected.)
  • Page 26 FX2N-64CL-M CC-Link/LT Master Block System Configuration 4 MEMO...
  • Page 27: Handling Cautions

    FX2N-64CL-M CC-Link/LT Master Block Handling Cautions 5 Handling Cautions INSTALLATION PRECAUTIONS • Use the FX -64CL-M in an environment with the general specifications described in this manual. If the FX -64CL-M is used in any other environment, thus, electrical shock, fire, malfunction, product damage or product deterioration may occur.
  • Page 28: Installation

    FX2N-64CL-M CC-Link/LT Master Block Handling Cautions 5 Installation The FX -64CL-M can be attached via DIN rail or attached directly with screws. The installation procedure in each case is described below. 5.1.1 Installation direction • Do not install the master block on floor surfaces, ceiling surfaces or in a horizontal direction. If the master block is installed in such a way, its temperature may rise.
  • Page 29: Connection Of Cables, Connectors And Terminating Resistors

    FX2N-64CL-M CC-Link/LT Master Block Connection of Cables, Connectors and Terminating Resistors 6 Connection of Cables, Connectors and Terminating Resistors Connect the master station, power adapter and remote stations with flat cables dedicated to CC-Link/LT and connectors for dedicated flat cables. Lay out the master block on one side of the trunk line.
  • Page 30: Connection Of Units Using Flat Cables Dedicated To Cc-Link/Lt

    FX2N-64CL-M CC-Link/LT Master Block Connection of Cables, Connectors and Terminating Resistors 6 Connection of units using flat cables dedicated to CC-Link/LT This paragraph explains the connection method using flat cables dedicated to CC-Link/LT. 1) The connection order of dedicated flat cables has no relevance to the station No. 2) Lay out the FX -64CL-M at either end of the trunk line.
  • Page 31 FX2N-64CL-M CC-Link/LT Master Block Connection of Cables, Connectors and Terminating Resistors 6 2) Attachment procedure The procedure is shown below. a) Terminal processing procedure 2 ) C l o s e t h e c o v e r t o f i r m l y h o l d t h e 1 ) C o r r e c t l y s e t t h e d e d i c a t e d f l a t 3 ) C o m b i n e t h e b o d y w i t h t h e c o v e r , d e d i c a t e d f l a t c a b l e .
  • Page 32: How To Attach Terminating Resistor

    FX2N-64CL-M CC-Link/LT Master Block Connection of Cables, Connectors and Terminating Resistors 6 6.2.1 How to attach terminating resistor This paragraph explains how to attach terminating resistors to either end of the CC-Link/LT system. Attach terminating resistors to the connectors placed to flat cables dedicated to CC-Link/LT. Terminating resistor Connector for dedicated flat cable...
  • Page 33: Wiring Check

    FX2N-64CL-M CC-Link/LT Master Block Connection of Cables, Connectors and Terminating Resistors 6 6.2.2 Wiring check Confirm the wiring between remote I/O units and external equipment. Example of wiring check The figure below shows an example in which the head I/O No. in the FX -64CL-M is X020/ Y020 and 4-point mode is selected.
  • Page 34 FX2N-64CL-M CC-Link/LT Master Block Connection of Cables, Connectors and Terminating Resistors 6 MEMO...
  • Page 35: Various Modes

    FX2N-64CL-M CC-Link/LT Master Block Various Modes 7 Various Modes The FX -64CL-M has ONLINE, CONFIG and TEST modes. Each mode can be selected using the appropriate DIP switch. (Turn OFF the power to the PLC before setting the DIP switches.) ONLINE mode (DIP switch bit 6 = OFF, bit 7 = OFF) In ONLINE mode, the FX -64CL-M will execute the data link in the CC-Link/LT system.
  • Page 36 FX2N-64CL-M CC-Link/LT Master Block Various Modes 7 MEMO...
  • Page 37: Assignment Of I/O Nos

    FX2N-64CL-M CC-Link/LT Master Block Assignment of I/O Nos. 8 Assignment of I/O Nos. The FX -64CL-M assigns I/O information for remote I/O units to devices X (input) and Y (output) in the PLC. The I/O Nos. are assigned in CONFIG mode. At this time, the I/O Nos.
  • Page 38: Example Of I/O No. Assignment

    FX2N-64CL-M CC-Link/LT Master Block Assignment of I/O Nos. 8 Example of I/O No. assignment This paragraph describes I/O No. assignment in the configuration example shown below. I/O extension Master block block -32MT -16EX -64CL-M Station No. when the 16-point mode is selected 4 input 2 output 16 input...
  • Page 39: Automatic I/O No. Assignment

    FX2N-64CL-M CC-Link/LT Master Block Assignment of I/O Nos. 8 Automatic I/O No. assignment The I/O Nos. can be assigned automatically in the CONFIG mode. Parameter settings and sequence programs are not necessary for this assignment. 8.3.1 Automatic I/O No. assignment procedure Execute the steps 1) to 3) below to automatically assign the I/O Nos.
  • Page 40: Reserved Station Setting Method

    FX2N-64CL-M CC-Link/LT Master Block Assignment of I/O Nos. 8 8.4.1 Reserved station setting method Set reserved stations using the steps 1) to 4) below. 1) Set the FX -64CL-M to the CONFIG Mode (by setting bit 6 of the DIP switch to ON and setting bit 7 to OFF).
  • Page 41: Editing The Detailed Remote Station Information

    FX2N-64CL-M CC-Link/LT Master Block Assignment of I/O Nos. 8 Editing the detailed remote station information After assigning the I/O Nos. in the CONFIG mode, the I/O No. assignment in each station No. can be edited. With this function, the number of I/O points can be changed, and the I/O Nos. can be assigned to unconnected station Nos.
  • Page 42 FX2N-64CL-M CC-Link/LT Master Block Assignment of I/O Nos. 8 Configuration of detailed remote station information Function 1(ON) 0(OFF) 00001:1point 00101:5points 01001: 9points 01101:13points 00010:2points 00110:6points 01010:10points 01110:14points 00011:3points Number of I/O points 00111:7points 01011:11points 01111:15points 00100:4points 01000:8points 01100:12points 10000:16points The bits above are in the order "b4, b3, b2, b1, b0". b5 to b7 (Setting prohibited) Set these bits to 0.
  • Page 43: Data Link Processing Time

    FX2N-64CL-M CC-Link/LT Master Block Data Link Processing Time 9 Data Link Processing Time This section explains the link scan time and transmission delay time. Link scan time This paragraph explains the link scan time for the CC-Link/LT network. 9.1.1 Link scan time calculation formula Link scan time = a + ( b ×...
  • Page 44: Transmission Delay Time

    FX2N-64CL-M CC-Link/LT Master Block Data Link Processing Time 9 9.1.2 Transmission delay time The transmission delay time (the time until data is received) (including the time for communication between the main unit and FX -64CL-M) can be calculated by the following formula.
  • Page 45: Assignment Of Buffer Memory

    FX2N-64CL-M CC-Link/LT Master Block Model Assignment of Buffer Memory 10 Assignment of Buffer Memory Data transfer between the PLC main unit and FX -64CL-M is executed by a program in the PLC. Use the FROM instruction to read data saved in the FX -64CL-M to the main unit.
  • Page 46: Details Of Buffer Memory

    FX2N-64CL-M CC-Link/LT Master Block Model Assignment of Buffer Memory 10 10.2 Details of buffer memory 10.2.1 Remote station connection information [BFM #0 (0h) to #3 (3h)] The connection status of remote stations connected in the system are stored in BFM #0 to BFM #3 (bits for connected stations are ON).
  • Page 47 FX2N-64CL-M CC-Link/LT Master Block Model Assignment of Buffer Memory 10 Handling in the CONFIG mode In the CONFIG mode, if the detailed remote station information [BFM #32 (20h) to #95 (5Fh)] is edited, and if the detailed remote station information is inconsistent with remote stations actually connected at the time of power ON as a result of the editing, there will be a data link error.
  • Page 48: Remote I/O Error Information [Bfm #8 (8H) To #11 (Bh)]

    FX2N-64CL-M CC-Link/LT Master Block Model Assignment of Buffer Memory 10 10.2.3 Remote I/O error information [BFM #8 (8h) to #11 (Bh)] The remote I/O error occurrence status is stored here. (Bits for stations having I/O error are ON.) For the type of error, refer to the instruction manual of each remote station. The station No.
  • Page 49: Number Of Required Input Blocks [Bfm #20 (14H)]

    FX2N-64CL-M CC-Link/LT Master Block Model Assignment of Buffer Memory 10 10.2.5 Number of required input blocks [BFM #20 (14h)] The number of input blocks (8 points/block) required to assign the I/O Nos. of remote stations is stored here. 10.2.6 Number of required output blocks [BFM #21 (15h)] The number of output blocks (8 points/block) required to assign the I/O Nos.
  • Page 50: Command [Bfm #27 (1Bh)]

    FX2N-64CL-M CC-Link/LT Master Block Model Assignment of Buffer Memory 10 10.2.9 Command [BFM #27 (1Bh)] Command gives the FX -64CL-M instructions to stop/restart the data link and write data to the EEPROM. A function is assigned to each bit of the buffer memory [BFM #27 (1Bh)]. Each function is executed according to the 0 (OFF)/1 (ON) status of each bit.
  • Page 51: 10Status Information [Bfm #28 (1Ch)]

    FX2N-64CL-M CC-Link/LT Master Block Model Assignment of Buffer Memory 10 10.2.10 Status information [BFM #28 (1Ch)] Status information such as the RUN and link status is stored here. Bits in the buffer memory contains status information for the FX -64CL-M. The status is indicated by the 0 (OFF)/1 (ON) status of each bit.
  • Page 52: 11Detailed Error Information [Bfm #29 (1Dh)]

    FX2N-64CL-M CC-Link/LT Master Block Model Assignment of Buffer Memory 10 10.2.11 Detailed error information [BFM #29 (1Dh)] Each type of error is assigned to a bit of the buffer memory [BFM #29 (1Dh)]. The status is indicated by the 0 (OFF)/1 (ON) status of each bit. Error flag restoration Function Description...
  • Page 53 FX2N-64CL-M CC-Link/LT Master Block Model Assignment of Buffer Memory 10 Error flag restoration Function Description operation In the case that a request to write to the EEPROM is given in any mode other than the Turns ON when EEPROM write error or CONFIG mode, the error flag read error has occurred or when the is automatically restored when...
  • Page 54: 12Model Code [Bfm #30 (1Eh)]

    FX2N-64CL-M CC-Link/LT Master Block Model Assignment of Buffer Memory 10 10.2.12 Model code [BFM #30 (1Eh)] The model code (K7120) of the FX -64CL-M is stored here. 10.2.13 Detailed remote station information [BFM #32 (20h) to #95 (5Fh)] The information (I/O type, number of points) on remote stations is stored here. In the CONFIG mode, the contents of these buffers can be changed.
  • Page 55 FX2N-64CL-M CC-Link/LT Master Block Model Assignment of Buffer Memory 10 2) Input flag and output flag Whether a corresponding I/O unit is an input unit, output unit or composite I/O unit, it is stored here. b9: Output flag b8: Input flag Unit type Input unit Output unit...
  • Page 56 FX2N-64CL-M CC-Link/LT Master Block Model Assignment of Buffer Memory 10 6) Reserved station flag Specification as a reserved station is stored here. When specifying the station as reserved in the CONFIG mode, write "1 (ON)". (For the details on reserved stations, refer to "8.4 Specification of reserved station".) Reserved station flag This station is not specified as a reserved one.
  • Page 57: Program Example

    FX2N-64CL-M CC-Link/LT Master Block Program Example 11 Program Example This section describes a program in the PLC for the configuration shown in "11.2 System configuration". In this example, the I/O Nos. are assigned automatically in the CONFIG mode. The specification as reserved station and the detailed remote station information are not changed.
  • Page 58 FX2N-64CL-M CC-Link/LT Master Block Program Example 11 WIRING PRECAUTIONS • Make sure to shut down all power supplies before starting the installation or wiring work. If the power is not disconnected from all sources an electric shock or serious product damage may occur.
  • Page 59: System Startup Procedure

    FX2N-64CL-M CC-Link/LT Master Block Program Example 11 11.1 System Startup Procedure Start Refer to Install the FX -64CL-M, remote I/O units and power adapter to the control panel and machine. Section 5. Connect the FX -64CL-M, remote I/O units and power adapter with the dedicated flat cables. Refer to Section 6.
  • Page 60: System Configuration

    FX2N-64CL-M CC-Link/LT Master Block Program Example 11 11.2 System configuration Main unit Master block -32MR -64CL-M X000 to X017 General-purpose power supply Y000 to Y017 Power adapter 24V DC Terminating resistor Terminating resistor Remote station (station No. 2) Remote station (station No.1) CL1XY8-DR1B2 CL1XY8-DR1B2 X024 to X027...
  • Page 61: Device Assignment

    FX2N-64CL-M CC-Link/LT Master Block Program Example 11 11.3 Device assignment In this example, devices in the PLC are used as follows. Device Description X000 CC-Link/LT control start signal Input (X) X001 Data link stop instruction signal X002 Data link restart instruction signal Y000 Remote station connection error occurrence Y001 Data link error occurrence Y002 All-station data link error occurrence...
  • Page 62: Program Example

    FX2N-64CL-M CC-Link/LT Master Block Program Example 11 11.4 Program example M8000 Reads the error FROM station information. To easily Reads the detailed FROM K4M10 monitor the error information. nerwork, output Data link error has select error < > Y000 occurred. flags to external The remote station...
  • Page 63: Troubleshooting

    FX2N-64CL-M CC-Link/LT Master Block Troubleshooting 12 Troubleshooting 12.1 Status of each station during abnormal operation The table below shows the status of each station when an abnormal operation has occurred. Status of each station Data link status Master station Remote station Remote input Remote output Input Output...
  • Page 64: Confirmation Of Status Based On Status Indicator Leds And Countermeasures

    FX2N-64CL-M CC-Link/LT Master Block Troubleshooting 12 12.2 Confirmation of status based on status indicator LEDs and countermeasures 12.2.1 ONLINE mode The table below shows the descriptions of errors during in the ONLINE mode (bits 6 and 7 of the DIP switches are OFF in the FX -64CL-M), indicated by the status indicator LEDs and their countermeasures.
  • Page 65: Config Mode

    • If there is no problem in the capacity of the power abnormal for the PLC and the supplied 5V DC power, contact Power is interrupted an office of MITSUBISHI ELECTRIC SYSTEM & SERVICE, CO., LTD. Lit: Communication speed setting • Confirm the DIP switch setting, reset power.
  • Page 66: Test Mode (Self-Loop-Back Test)

    • If there is no problem in the capacity of the power abnormal for the PLC and the supplied 5V DC power, contact Power is interrupted an office of MITSUBISHI ELECTRIC SYSTEM & SERVICE, CO., LTD. Lit: Communication speed setting error occurred •...
  • Page 67: Countermeasures Based On Detailed Error Information

    FX2N-64CL-M CC-Link/LT Master Block Troubleshooting 12 12.3 Countermeasures based on detailed error information The contents of error flags indicated by the BFM #29 (1Dh) and countermeasures against them are as shown below. Description Countermeasures Securely connect the FX -64CL-M and remote I/O units.
  • Page 68 FX2N-64CL-M CC-Link/LT Master Block Troubleshooting 12 Description Countermeasures • Return the DIP switch setting to the status at the time of power ON. Turns ON when the DIP switch setting is • If the DIP switch setting should be changed during operation. changed, change the DIP switch setting, reset power.
  • Page 69: Self-Loop-Back Test

    FX2N-64CL-M CC-Link/LT Master Block Troubleshooting 12 12.4 Self-loop-back test In the self-loop-back test, the FX -64CL-M checks whether it is operating normal by receiving data sent by itself. In this test, it is not necessary to connect remote stations. (Connect the FX -64CL-M to the power adapter, then set to ON the communication power.) •...
  • Page 70 • If there is no problem in the capacity of the power Power is for the PLC and the supplied 5V DC power, contact interrupted an office of MITSUBISHI ELECTRIC SYSTEM & SERVICE, CO., LTD. :Communication speed setting error • Confirm the operation setting switch setting, reset occurred power.
  • Page 71: Prevention Of Erroneous Inputs To And Outputs From Remote I/O Unit

    FX2N-64CL-M CC-Link/LT Master Block Troubleshooting 12 12.5 Prevention of erroneous inputs to and outputs from remote I/O unit In order to prevent erroneous inputs to and outputs from remote I/O units, design the system under consideration of the contents described below. 1) When setting the power to ON or OFF Set the power of remote I/O units to ON (the power of the power adapter) first, then start the data link.
  • Page 72 FX2N-64CL-M CC-Link/LT Master Block Troubleshooting 12 b) Countermeasures against erroneous input From the same power supply, wire the power supply unit, the stabilized power supply and the external power supply to the input area for AC inputs. Master PLC main unit unit Remote I/O unit External...
  • Page 73 USER’S MANUAL (Detailed Volume) -64CL-M CC-Link/LT Master Block HEAD OFFICE: MITSUBISHI DENKI BLDG MARUNOUCHI TOKYO 100-8310 HIMEJI WORKS: 840, CHIYODA CHO, HIMEJI, JAPAN Effective Jan. 2003 Specifications are subject JY997D08501A to change without notice. (MEE)
  • Page 74 Phone: +380 (0)44 / 494 33 55 Fax: +380 (0)44 / 494-33-66 Mitsubishi Electric Europe B.V. /// FA - European Business Group /// Gothaer Straße 8 /// D-40880 Ratingen /// Germany Tel.: +49(0)2102-4860 /// Fax: +49(0)2102-4861120 /// info@mitsubishi-automation.com /// www.mitsubishi-automation.com...