Mitsubishi Electric C80 series Maintenance Manual page 122

Hide thumbs Also See for C80 series:
Table of Contents

Advertisement

C80 Series Maintenance Manual
6 Replacing Each Unit
(d) The backup will start.
<Example>
PLC CPU/CNC CPU data has been backed up processing in the data name of "16062304".
(e) The dialog box will be displayed when the backup is completed. Press [OK] to complete the process.
(2) Turn off the NC.
(3) Exchange the CNC CPU.
(4) Initialize the CNC CPU.
Rotary switch 1
(SW1)
(a) With the power OFF, set SW1 to "7" and then turn the power ON.
(b) When the minus sign (-) appears on the right end of the dot matrix display, turn the power OFF.
(c) Set SW1 to "C" and then turn the power ON.
(d) When "y" is displayed on the right end of the dot matrix display, turn the power OFF.
(e) Set SW1 to "0" and then turn the power ON.
<Note>
After initialization, the IP address will be set to "192.168.200.1".
The initial screen after the initialization is displayed in English.
93
IB-1501454-C

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents