Uninterruptible Power Supply Unit UPS6
UPS6 installation consists of installation following units:
EMC Filter ME-MAX/NEF/QUINT20A;
Primary-Switched Power Supply Unit QUINT-PS/1AC/24DC/20;
Uninterruptible Power Supply Unit for Universal Use QUINT-DC-UPS/24DC/20;
Battery Module 24 V DC, 3.4 Ah QUINT-BAT/24DC/3.4AH (7.2 or 12 AH).
Technical specification of UPS6 is given in
For connection of the units see also connection diagram enclosed in
Installation of the Primary-Switched Power Supply Unit
QUINT-PS/1AC/24DC/20
Table 3. Structure
No.
Comments
1
AC input: 85...264 V AC input voltage, 45...65 Hz frequency
2
DC output: 24 V DC output voltage (default), can be set between 18 and 29.5 V DC
3
Active POWER BOOST switching output
4
DC OK output active
5
DC OK output floating
6
Potentiometer (covered) 18V DC...29.5 V DC
7
DC OK LED
8
BOOST LED
9
Universal DIN rail adapter UTA 107/30
Fig. 8. View of UPS6
Chapter 3
.
Fig. 9. Structure
Workstations Installation