Network Settings - Siemens SIMATIC PCS 7 Configuration Manual

Process control system compendium part a - configuration guidelines v8.2
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Preparation and administration
4.3 Installation
If a computer installation is being performed manually then the requirements and the procedure
for this must be observed. Information on this can be found in the "PCS 7 Readme"
support.industry.siemens.com/cs/ww/en/view/109478781) documentation and in the
"SIMATIC Process Control System PCS 7 - PC Configuration
support.industry.siemens.com/cs/ww/en/view/109485951)" manual.
4.3.5

Network settings

Address management
Following the PCS 7 installation, check the addresses and make any settings which may be
required. Systematic assignment of the addresses at the start of the project will make
configuration, commissioning, plant expansion, and maintenance easier.
Record the assigned addresses in a table like the one shown below, for example, and keep
them up to date:
Name
Name
Subproject
PC station/
AS station
25_ES
ES26
20_OS
SERVER1A
20_OS
SERVER1B
21_CL
CLIENT01
21_CL
CLIENT02
21_CL
CLIENT03
21_CL
CLIENT04
01_Plant_A
AS1_H
01_Plant_A
AS1_H
02_Plant_B
AS2
-
Scalance20
-
Scalance10
Setting the transmission rate and operating mode in the network
Siemens devices, including Industrial Ethernet switches (ScalanceX) and the Industrial
Ethernet CPs (CP 443-1 as of version 1EX10) are factory set for automatic detection of the
parameters for transmission rate and operating mode (autosensing, autonegotiation).
Autosensing describes the property of network components to automatically interpret an
incoming transmission signal. In this case, the device independently determines if the signal
has a data rate of 10 Mbps, 100 Mbps, or 1,000 Mbps. No explicit setting is required related
30
Terminal bus
Plant bus
IP address
IP address
172.20.1.26
172.10.1.126
172.20.1.xx
172.10.1.xx
172.20.1.xx
172.10.1.xx
172.20.1.xx
-
172.20.1.xx
-
172.20.1.xx
-
172.20.1.xx
-
-
-
-
-
-
-
172.20.1.xx
-
-
172.10.1.xx
(https://
Plant bus PC compo‐
nents
(e.g. CP1623)
MAC address
08-00-06-01-00-26
08-00-06-01-00-xx
08-00-06-01-00-xx
-
-
-
-
-
-
-
-
-
Compendium Part A - Configuration Guidelines (V8.2)
Configuration Manual, 08/2016, A5E38166869-AA
(https://
Plant bus AS compo‐
nents
(e.g. CP443-1)
MAC address
-
-
-
-
-
-
-
08-00-06-01-01-10
08-00-06-01-01-11
08-00-06-01-01-26
-
-