Network Variable - Samsung MR-DH00 Technical Data Book

Dvm control system
Hide thumbs Also See for MR-DH00:
Table of Contents

Advertisement

9) Network variable

(1) Indoor unit/ ERV/ AHU kit object
No.
Name
1
nviONOff
2
NviApplicMode
3
nviSetpoint
4
nviFanStatus
5
nviERVMode
6
nviFilterReset
7
nviUserLockout
8
nviOccOpMode
9
nviCoolTempLock
10
nviHeatTempLock
11
nvoSpaceTemp
12
nvoApplicMode
13
nvoSetpoint
14
nvoOnOff
15
nvoFanStatus
16
nvoERVMode
17
nvoErrorCode
18
nvoDeviceAlarm
19
nvoOccOpMode
20
nvoCoolTempLock
21
nvoHeatTempLock
22
nvoUserLockout
23
nvoEnergyConp
24
nvoEnergyCon
25
nvoRuntimep
26
nvoRuntime
27
nvoDevListDesc
(2) DVM system object
No.
Name
1
nviDigitalOut[6]
2
nviAllOff
3
nvoDigitalOut[6]
4
nvoDigitalIn[8]
5
nvoSystemLock
6
nvoDMS2Alarm
7
nvoSystemAlarm
(3) Configuration properties
No.
Name
1
nciSndHrtBt
2
nciMinOutTm
3
nciMinDeltaTemp
4
nciDelayStatrup
Type
M/O
SNVT_switch
O
SNVT_hvac_mode
O
SNVT_temp_p
O
SNVT_switch
O
SNVT_count
O
SNVT_switch
O
SNVT_switch
O
SNVT_switch
O
SNVT_switch
O
SNVT_switch
O
SNVT_temp_p
M
SNVT_hvac_mode
O
SNVT_temp_p
O
SNVT_switch
O
SNVT_switch
O
SNVT_count
O
SNVT_count
O
SNVT_state
O
SNVT_switch
O
SNVT_switch
O
SNVT_switch
O
SNVT_switch
O
SNVT_elec_kwh_l
O
SNVT_elec_kwh_l
O
SNVT_time_hour
O
SNVT_time_hour
O
SNVT_str_asc
O
Type
M/O
SNVT_ switch
O
SNVT_hvac_emerg
O
SNVT_ switch
O
SNVT_ switch
O
SNVT_ switch
O
SNVT_ count
O
SNVT_ count
O
Type
M/O
SNVT_time_sec
O
SNVT_time_sec
O
SNVT_temp_p
O
SNVT_time_sec
O
Description
ON/OFF command
Setting operating mode
Setting desire temperature
Setting fan speed
Setting ERV operation mode
Filter reset command
Setting the restriction of remote control use
Setting cooling only mode / heating only mode
Setting the low temperature limit
Setting the high temperature limit
Display indoor temperature
Display operating mode
Display desire temperature
Display ON/OFF status
Display fan speed
Display ERV operating mode
Display Error code
Remote control lock, Filter sign, Thermo ON/OFF,
Error occurrence status display
Cooling only/Heating only setup status display
Display low temperature limit setting status
Display high temperature limit setting status
Display the restriction of remote control use
Display electricity usage (Basic date)
Display used hours (Basic date)
Indoor unit HW information
Description
Control Digital output of DMS
Control all indoor unit / ERV OFF
Display Digital output status of DMS
Display Digital input status of DMS
Display System Lock status of DMS
Display communication error of the sub device
connected to DMS
Display error satus
Description
Send Heartbeat
Minimum Send Time
Min. difference before update
Delay time after a power-up
153

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents