2.2 SPECIFICATIONS

TYPE TESTS

TEST
Dielectric voltage withstand
Impulse voltage withstand
2
Damped oscillatory
Electrostatic discharge
RF immunity
Fast transient disturbance
Surge immunity
Conducted RF immunity
Power frequency immunity
Voltage interruption and ripple DC
Radiated and conducted emissions
Sinusoidal vibration
Shock and bump
Seismic
Power magnetic immunity
Pulse magnetic immunity
Damped magnetic immunity
Voltage dip and interruption
Damped oscillatory
Conducted RF immunity, 0 to 150 kHz
Voltage ripple
Ingress protection
Cold
Hot
Humidity
Damped oscillatory
RF immunity
Safety
Safety
Safety
2-14
REFERENCE STANDARD
EN60255-5
EN60255-5
IEC61000-4-18 / IEC60255-22-1
EN61000-4-2 / IEC60255-22-2
EN61000-4-3 / IEC60255-22-3
EN61000-4-4 / IEC60255-22-4
EN61000-4-5 / IEC60255-22-5
EN61000-4-6 / IEC60255-22-6
EN61000-4-7 / IEC60255-22-7
IEC60255-11
CISPR11 / CISPR22 / IEC60255-25
IEC60255-21-1
IEC60255-21-2
IEC60255-21-3
IEC61000-4-8
IEC61000-4-9
IEC61000-4-10
IEC61000-4-11
IEC61000-4-12
IEC61000-4-16
IEC61000-4-17
IEC60529
IEC60068-2-1
IEC60068-2-2
IEC60068-2-30
IEEE/ANSI C37.90.1
IEEE/ANSIC37.90.2
UL508
UL C22.2-14
UL1053
C30 Controller System
2 PRODUCT DESCRIPTION
TEST LEVEL
2.3 kV
5 kV
2.5 kV CM, 1 kV DM
Level 3
Level 3
Class A and B
Level 3 and 4
Level 3
Class A and B
12% ripple, 200 ms interrupts
Class A
Class 1
Class 1
Class 1
Level 5
Level 4
Level 4
0, 40, 70, 80% dips; 250 / 300 cycle interrupts
2.5 kV CM, 1 kV DM
Level 4
15% ripple
IP40 front, IP10 back
–40°C for 16 hours
85°C for 16 hours
6 day, variant 1
2.5 kV, 1 MHz
20 V/m, 80 MHz to 1 GHz
e83849 NKCR
e83849 NKCR7
e83849 NKCR