CHAPTER 6: ACTUAL VALUES
is a counter for total messages received with an error on Port B (PRP frame, but port received through
Mismatches Port B
and LAN ID in the frame do not match).
6.3.21 TxGOOSE status
ACTUAL VALUES STATUS TxGOOSE STATUS
TxGOOSE STATUS
The C30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
This status is relevant to R-GOOSE reception when configured for SSM or ASM reception modes. It is not relevant for GOOSE
or for R-GOOSE in unicast reception mode.
— The unicast mode of R-GOOSE transmission requires Address Resolution Protocol (ARP) for the resolution of the
ARP
network layer address into the MAC layer address. R-TxGOOSE## ARP status On indicates that ARP responses are being
received and the destination MAC address for R-GOOSE transmissions has been obtained. This status remains Off if
TxGOOSE## is not configured for R-GOOSE. It also remains Off if setting R-TxGOOSE1 DST IP is set to a multicast address. In
the case where setting R-TxGOOSE1 DST IP is configured with a unicast address and this status indicates Off, TxGOOSE##
transmission will be off, and therefore communication network diagnosis needs to be carried out.
This status is only applicable for R-GOOSE transmission with setting R-TxGOOSE1 DST IP set to a unicast IP address. It is not
applicable for GOOSE or for R-GOOSE when setting R-TxGOOSE1 DST IP is multicast.
6.4 Metering
6.4.1 FlexElements
ACTUAL VALUES METERING FLEXELEMENTS FLEXELEMENT 1(8)
FLEXELEMENT 1
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
Table 6-1: FlexElement base units
Base unit
DCmA
FREQUENCY
PHASE ANGLE
POWER FACTOR
RTDs
SOURCE CURRENT
SOURCE POWER
SOURCE VOLTAGE
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
R-TxGOOSE 1
ARP:
Off
R-TxGOOSE 16
ARP:
Off
FLEXELEMENT 1
OpSig:
0.000
Description
BASE = maximum value of the DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs.
f
= 1 Hz
BASE
ϕ
= 360 degrees (see the UR angle referencing convention)
BASE
PF
= 1.00
BASE
BASE = 100°C
I
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
P
= maximum value of V
BASE
BASE
V
= maximum nominal primary RMS value of the +IN and –IN inputs
BASE
Range: On, Off
Range: On, Off
× I
for the +IN and –IN inputs
BASE