GE C30 Instruction Manual page 332

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

SYSTEM SETUP
BREAKER 1 ΦB CLOSED
pole, this input is used to track the breaker phase B closed position as outlined for phase A.
BREAKER 1 ΦB OPENED
pole, this input is used to track the breaker phase B opened position as outlined for phase A.
BREAKER 1 ΦC CLOSED
pole, this input is used to track the breaker phase C closed position as outlined for phase A.
BREAKER 1 ΦC OPENED
pole, this input is used to track the breaker phase C opened position as outlined for phase A.
BREAKER 1 TOPERATE
and 52/b auxiliary contacts during breaker operation. If transient disagreement still exists after this time has expired, the
BREAKER 1 BAD STATUS
BREAKER 1 EXT ALARM
reporting contact. While the selected operand is active, the
BREAKER 1 ALARM DELAY
pole position tracking operands does not declare a pole disagreement. This allows for non-simultaneous operation of the
poles.
BREAKER 1 OPEN SEAL-IN
Trip Out element or a manual open command to the circuit breaker.
MANUAL CLOSE RECAL1 TIME
manual close command to the circuit breaker.
BREAKER 1 OUT OF SV
BREAKER 1 RACKED-IN
5
racked-in or racked-out status is used to indicate dynamically the status of breaker symbol, only applied in the single-line
diagram in the graphical front panel. If this setting is set to Off, the racked status is not considered.
5-138
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— If the mode is selected as three-pole, this setting has no function. If the mode is selected as single-
— This setting specifies the required interval to overcome transient disagreement between the 52/a
FlexLogic operand is asserted for alarm or blocking purposes.
— This setting selects an operand, usually an external contact input connected to a breaker alarm
— This setting specifies the delay interval during which a disagreement of status among the three-
— This setting specifies the seal-in time of the three-pole open command initiated by either the
— This setting specifies the seal-in time of the close commands due to an operator-initiated
— Selects an operand indicating that breaker 1 is out-of-service.
— This setting selects a contact input to show whether the breaker is racked-in or racked-out. The
operand is activated.
BREAKER 1 TROUBLE
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS