Rexroth Frequency Converter EFC 3600
Acc. / Dec. time
terminal 2
Inactive
Inactive
Active
Active
Fig.8-3: Acc. / Dec. time options
● 7: 3-wire running control
Used to control the frequency converter in 3-wire control mode. See parameter
[E0.00].
● 8: Freewheeling to stop enabled
"Freewheeling to stop enabled" generates a STOP command and forces the fre‐
quency converter to freewheel to stop regardless of the stopping mode configured
by [b1.40].
● 9: Frequency increment UP command
● 10: Frequency decrement DOWN command
● 11: Zeroing of external terminal frequency setting
The above three functions are used to change the frequency set with terminals UP /
DOWN or clear the frequency to 0 Hz by the zeroing terminal. See parameters
[S3.32] and [S3.33].
● 12: Reserved
● 13: Stopping DC braking enabled
This function is used when stopping mode is set with [b1.40]=0. For more details,
see parameters [b1.40] ~ [b1.43].
● 14: Reserved
● 15: Simple PLC prohibited
If the PLC is running and this terminal is switched on, the frequency converter will
stop output and motor freewheeling to stop. While if this terminal is switched off, the
frequency converter will stay standstill until the next RUN command is activated.
[E2.30]
≠0
≠0
Acc. / Dec. time
terminal 1
Inactive
Active
Inactive
Active
Xi=15
OFF
ON
Selected Acc. / Dec. time
Acceleration time 1 is selected ([b1.20])
Deceleration time 1 is selected ([b1.21])
Acceleration time 2 is selected ([E2.00])
Deceleration time 2 is selected ([E2.01])
Acceleration time 3 is selected ([E2.02])
Deceleration time 3 is selected (E2.03])
Acceleration time 4 is selected ([E2.04])
Deceleration time 4 is selected ([E2.05])
Simple PLC status
Bosch Rexroth AG
Parameter Settings
Running
Inactive
95/235