Analog input curve configuration
Function
Name
code
Analog setting
E0.20
curve selection
E0.21
Curve 1 min. reference 0.0 % ~ [E0.23]
Frequency correspond‐
E0.22
ing to curve 1 min. ref‐
erence
E0.23
Curve 1 max. reference [E0.21] ~ 100.0 %
Frequency correspond‐
E0.24
ing to curve 1 max. ref‐
erence
E0.25
Curve 2 min. reference 0.0 % ~ [E0.27]
Frequency correspond‐
E0.26
ing to curve 2 min. ref‐
erence
E0.27
Curve 2 max. reference [E0.25] ~ 100.0 %
Setting range
0 ~ 3
0 = AIC-reference
characteristic curve 1;
AIV-reference charac‐
teristic curve 1
1 = AIC-reference
characteristic curve 1;
AIV-reference charac‐
teristic curve 2
2 = AIC-reference
characteristic curve 2;
AIV-reference charac‐
teristic curve 1
3 = AIC-reference
characteristic curve 2;
AIV-reference charac‐
teristic curve 2
0.00 ~ [b1.06]
0.00 ~ [b1.06]
0.00 ~ [b1.06]
Bosch Rexroth AG
Appendix
Min.
Factory
Attribute
unit
default
1
0
0.10 % 0.00 %
0.01 Hz 0.00 Hz
100.00
0.10 %
%
50.00
0.01 Hz
Hz
0.10 % 0.00 %
0.01 Hz 0.00 Hz
100.00
0.10 %
%
RUN/
STOP
RUN/
STOP
RUN/
STOP
RUN/
STOP
RUN/
STOP
RUN/
STOP
RUN/
STOP
RUN/
STOP