Example - GE D60 Instruction Manual

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

PHASE DISTANCE APPLIED TO POWER TRANSFORMERS
Equations from the "Current Transformation" and "Voltage Transformation" columns are used to derive inputs to the three
(AB, BC, and CA) phase distance elements. For example, if the CTs are located at the delta side of the Delta-Wye 11
transformer, and a given zone is set to look through the transformer into the system connected to the Wye winding, the CT
location setting for that zone is set to Dy11 and the relay uses
distance element.
The current supervision pickup setting applies to the currents specified in the "Current Transformation" columns.
A distance zone originates at the location of the VTs (regardless of the location of the CTs). For information on settings see
the Application of Settings chapter.

9.2.2 Example

Consider the system shown.
9
Normally, in order to respond to the fault shown in the figure, a distance relay is applied at the relaying point X. The table
outlines the relay input signals at this location.
Table 9-10: Relay input signals at location X
Input
Primary
VA
100.4 kV ∠–7.32°
9-16
Figure 9-5: Sample system configuration
Secondary
38.25 V ∠–7.32°
D60 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 9: THEORY OF OPERATION
instead of a traditional I
- I
A
B
for the AB phase

Advertisement

Table of Contents
loading

Table of Contents