GE D60 Instruction Manual page 191

Line distance protection system
Hide thumbs Also See for D60:
Table of Contents

Advertisement

CHAPTER 5: SETTINGS
The Access Authorized Timeout setting represents the timeout delay remote setting access. It applies when the Remote
Settings Authorized setting is programmed to any operand except "On" or "Off." The state of the FlexLogic operand is
continuously monitored for an off-to-on transition. When this occurs, remote setting access is permitted, and the timer
programmed with the Access Authorized Timeout setting value is started. When this timer expires, remote setting access
is denied immediately. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout
is restarted. The status of this timer updates every five seconds.
5.3.1.3 EnerVista security
Enable the security management system
The EnerVista security system allows an administrator to manage access privileges of multiple users of EnerVista.
It is disabled by default to allow access to the device immediately after installation. When security is disabled, all users
have administrator access. GE recommends enabling the EnerVista security before placing the device in service.
To enable the security system and require password use:
1.
Select the Security > User Management menu to open the user management window.
2.
Enable the Enable Security check box in the lower-left corner to enable the security management system.
3.
Click the Ok button.
If you force password entry by using this feature, ensure that you know the Administrator password. If you do not
know the password and are locked out of the software, contact GE Grid Solutions for the default password of a UR
device. When using CyberSentry, the default password is "ChangeMe1#".
Security is now enabled for the EnerVista UR Setup software. Upon starting the software, users are now required to enter a
username and password.
Add a new user
The following pre-requisites are required to add user accounts to the EnerVista security management system:
The user adding the account must have administrator rights
The EnerVista security management system must be enabled (previous section)
To add a user account:
1.
Select the Security > User Management item from the top menu to open the user management window.
2.
Enter a username in the User field. The username must be four to 20 characters in length.