CHAPTER 2: PRODUCT DESCRIPTION
Rating factor (RF):
Frequency:
Voltage insulation:
Basic impulse level (BIL):
GPM-F-HM, GPM-F-L, GPM-F-R, GPM-S-B, AND GPM-S-G MODULE TYPE TESTS
Test
Dielectric voltage withstand
Impulse voltage withstand
Insulation
Damped oscillatory
Electrostatic discharge
RF immunity
Fast Transient Disturbance
Surge Immunity
Conducted RF Immunity
Voltage interruption and ripple DC
Radiated and conducted emissions
Sinusoidal vibration
Shock and Bump
Seismic
Power magnetic immunity
Pulse magnetic immunity
Damped magnetic immunity
Voltage dip and interruption
Voltage ripple
Ingress protection
Environmental (cold)
Environmental (dry heat)
Relative humidity cyclic
SWC oscillatory
SWC transients
RF immunity
ESD
Safety

2.5.9 Communication protocols

IEC 61850
IEC 61850:
RS232 (Enhanced and standard front panels)
Front port:
USB (Graphical front panel)
Front port:
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
3.0
20 Hz
600 V
10 kV
Reference standard
EN60255-5
EN60255-5
EN60255-5
IEC61000-4-18IEC60255-22-1
EN61000-4-2/IEC60255-22-2
EN61000-4-3/IEC60255-22-3
EN61000-4-4/IEC60255-22-4
EN61000-4-5/IEC60255-22-5
EN61000-4-6/IEC60255-22-6
IEC60255-11
CISPR11 / CISPR22 / IEC60255-25
IEC60255-21-1
IEC60255-21-2
IEC60255-21-3
IEC61000-4-8
IEC61000-4-9
IEC61000-4-10
IEC61000-4-11
IEC61000-4-17
IEC60529
IEC60068-2-1
IEC60068-2-2
IEC60068-2-30
IEEE/ANSI C37.90.1
IEEE/ANSI C37.90.1
IEEE/ANSIC37.90.2
IEEE/ANSIC37.90.3
UL508
UL C22.2-14
Supports IEC 61850 Edition 2.0. See the UR Family Communications Guide and its conformance
statements.
19.2 kbps, Modbus RTU
USB 2.0 type B
Test level
GPM-F types
GPM-S types
2.3 kV AC / 4.6 kV DC
2.3 kV AC / 3.3 kV DC
5 kV
5 kV
500 V DC
500 V DC
2.5 kV CM, 1 kV DM
2.5 kV CM, 1 kV DM
Level 4
Level 4
20 V/m
20 V/m
Class A and B
Class A and B
Level 4
Level 4
Level 3
Level 3
15% ripple,
15% ripple,
1 ms to 5 s interrupts
1 ms to 5 s interrupts
Class A
Class A
Class 2
Class 1
Class 2
Class 1
Class 2
Class 1
Level 5
Level 5
Level 4
Level 4
Level 4
Level 4
0%, 40%, 70%, 80% dips;
0%, 40%, 70%, 80% dips;
250/300 cycle interrupts
250/300 cycle interrupts
15% ripple
15% ripple
IP10
IP10
–40°C, 16 hrs
–40°C, 16 hrs
85°C, 16hrs
85°C, 16hrs
6 day, variant 1
6 day, variant 1
2.5 kV,1 MHz
2.5 kV,1 MHz
4 kV 2.5 kHz
4 kV 2.5 kHz
20 V/m
20 V/m
15 kV air / 8 kV contact
15 kV air / 8 kV contact
e83849 NKCR2
e83849 NKCR2
e83849 NKCR8
e83849 NKCR8