Diagnostic LEDs
AI Input Isolation
AI Input Insulation
User Connection
Cable and TB Holder
Module Replacement
Operating Voltage
Power Consumption
Dimensions
Weight
AO - Voltage mode LED, Current mode LED, Calibration LED
per channel
AI - Overflow and Underflow LED per each input, 24V Plug-in
status LED
The module Overflow and Underflow levels can be configured
to:
Current inputs: ±20mA / 4-20 mA
Voltage inputs: ±5 V / 0-5 V /1-5 V
General - Module error LED
1.5 kV between input and module logic
Insulation resistance 100 MΩ @ 500 V DC per IEC60255-5
4 Terminal Blocks (3.5mm pitch), Maximum 18 AWG
40-wire cable braid with Terminal Block holder connector, 26
AWG
Hot swap replacement– module extraction/insertion under
voltage
10.8-16 V DC and 3.3 V DC (from the motherboard connector)
Refer to Appendix D: ACE3600 Maximum Power Ratings.
37 mm W x 225 mm H x 180 mm D (1.5" W x 8.7" H x 7.1" D)
Approx. 0.34 Kg (0.75 Lb)
Specifications subject to change without notice.
15-7
Mixed Analog Module