Metering - GE F60 Instruction Manual

Ur series feeder protection system
Hide thumbs Also See for F60:
Table of Contents

Advertisement

2.2 SPECIFICATIONS
HI-Z
Detections:
2
RMS CURRENT: PHASE, NEUTRAL, AND GROUND
Accuracy at
0.1 to 2.0 × CT rating: ±0.25% of reading or ±0.1% of rated
> 2.0 × CT rating:
RMS VOLTAGE
Accuracy:
REAL POWER (WATTS)
Accuracy:
REACTIVE POWER (VARS)
Accuracy:
APPARENT POWER (VA)
Accuracy:
WATT-HOURS (POSITIVE AND NEGATIVE)
Accuracy:
Range:
Parameters:
Update rate:
VAR-HOURS (POSITIVE AND NEGATIVE)
Accuracy:
Range:
Parameters:
Update rate:
2-14
Arc Suspected, Arc Detected, Downed
Conductor, Phase Identification
(whichever is greater)
±1.0% of reading
±0.5% of reading from 10 to 208 V
±1.0% of reading at
–0.8 < PF ≤ –1.0 and 0.8 < PF ≤ 1.0
±1.0% of reading at –0.2 ≤ PF ≤ 0.2
±1.0% of reading
±2.0% of reading
6
±0 to 1 × 10
MWh
three-phase only
50 ms
±2.0% of reading
6
±0 to 1 × 10
Mvarh
three-phase only
50 ms
F60 Feeder Protection System
2 PRODUCT DESCRIPTION
PHASOR MEASUREMENT UNIT
Output format:
per IEEE C37.118 standard
Number of channels:
14 synchrophasors, 8 analogs, 16 digi-
tals
TVE (total vector error)
<1%
Triggering:
frequency, voltage, current, power, rate
of change of frequency, user-defined
Reporting rate:
1, 2, 5, 10, 12, 15, 20, 25, 30, 50, or 60
times per second
Number of clients:
One over TCP/IP port, two over UDP/IP
ports
AC ranges:
As indicated in appropriate specifications
sections
Network reporting format: 16-bit integer or 32-bit IEEE floating
point numbers
Network reporting style: rectangular (real and imaginary) or polar
(magnitude and angle) coordinates
Post-filtering:
none, 3-point, 5-point, 7-point
Calibration:
±5°
CURRENT HARMONICS
Harmonics:
2nd to 25th harmonic: per phase, dis-
played as a % of f
quency phasor)
THD: per phase, displayed as a % of f
Accuracy:
HARMONICS:
1. f
> 0.4pu: (0.20% + 0.035% / harmonic) of
1
reading or 0.15% of 100%, whichever is
greater
2. f
< 0.4pu: as above plus %error of f
1
THD:
1. f
> 0.4pu: (0.25% + 0.035% / harmonic) of
1
reading or 0.20% of 100%, whichever is
greater
2. f
< 0.4pu: as above plus %error of f
1
VOLTAGE HARMONICS
Harmonics:
2nd to 25th harmonic: per phase, dis-
played as a % of f
quency phasor)
THD: per phase, displayed as a % of f
Accuracy:
HARMONICS:
1. f
> 0.4pu: (0.20% + 0.035% / harmonic) of
1
reading or 0.15% of 100%, whichever is
greater
2. f
< 0.4pu: as above plus %error of f
1
THD:
1. f
> 0.4pu: (0.25% + 0.035% / harmonic) of
1
reading or 0.20% of 100%, whichever is
greater
2. f
< 0.4pu: as above plus %error of f
1
FREQUENCY
Accuracy at
V = 0.8 to 1.2 pu:
±0.01 Hz (when voltage signal is used
for frequency measurement)
I = 0.1 to 0.25 pu:
±0.05 Hz
I > 0.25 pu:
±0.02 Hz (when current signal is used for
frequency measurement)

2.2.4 METERING

(
fundamental fre-
1
1
1
1
(
fundamental fre-
1
1
1
1