ABB EXCOUNT-II User Manual page 15

Hide thumbs Also See for EXCOUNT-II:
Table of Contents

Advertisement

Error
Description
code
61
Low leakage current
62
High leakage current
70
Unstable leakage
current
80
Sensor not found
81
Transmission buffer
error
82
Connection lost
Suggested cause and action
The measured leakage current is too low. Check that the line
is correctly energised.
The measured leakage current is too high. Check that the line
is correctly energised. If so, try taking another measurement.
If the error persits, the arrester may be suspect.
A stable value for the leakage current cannot be measured.
A likley cause may be an unstable line voltage. Take new
measurements at another time.
The sensor ID was not recognised by any locally present
sensor. Try retransmitting again. If contact still cannot be
established, check:
a) the chosen sensor ID is present at this station
b) the distance to the sensor is not too far (max 60 m, but
can depend on interference from buildings and structures)
c) interference from a cellular/mobile phone
d) battery status to ensure the voltage in the transceiver
battery is not too low
Turn off the transceiver and re-start. If the error persists,
a serious internal fault has occurred with the Transceiver.
Contact your EXCOUNT-II service representative.
The sensor recognised it's ID but the connection was lost
during the transmission. Try re-transmiting again. If the error
persists, check:
a) the distance to the sensor is not too far (max 60m, but
can depend on interference from buildings and structures).
b) interference from a cellular/mobile phone.
c) battery status to ensure the voltage in the transceiver
battery is not too low.
2501en EXCOUNT-II Users Manual
Transceiver error codes