Frequency Setting By Analog Input (Terminal 1, 2, 4); Analog Input Selection (Pr.73, Pr.267) - Mitsubishi Electric F700 Instruction Manual

Hide thumbs Also See for F700:
Table of Contents

Advertisement

3.15 Frequency setting by analog input (terminal 1, 2, 4)

Purpose
Selection of voltage/current input
(terminal 1, 2, 4) Perform forward/
reverse rotation by analog input.
Adjust the main speed by analog
auxiliary input.
Noise elimination at the analog input Input filter
Adjustment (calibration) of analog
input frequency and voltage
(current)

3.15.1 Analog input selection (Pr.73, Pr.267)

You can select the function that switches between forward rotation and reverse rotation according to the
analog input selection specifications, the override function and the input signal polarity.
Parameter
Name
Number
73
Analog input selection
267
Terminal 4 input selection
The above parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 140)
(1) Selection of analog input selection
⋅ For the terminals 1, 2, 4 used for analog input, voltage input (0 to 5V, 0 to 10V) or current input (4 to 20mA) can
be selected.
⋅ Refer to the following table and set Pr. 73 and Pr. 267. (
Pr. 73
AU Signal
Setting
0
1 (initial value)
2
3
4
5
6
7
OFF
10
(absence)
11
12
13
14
15
16
17
0
1
2
3
4
5
6
7
ON
(presence)
10
11
12
13
14
15
16
17
* Indicates that a frequency command signal of negative polarity is not accepted.
Parameter that must be set
Analog input selection
Analog auxliary input and
compensation (added compensation
and override function)
Bias and gain of frequency setting
voltage (current)
Initial Value
1
0
Terminal 2
Terminal 1
Terminal 4 Input
Input
Input
0 to ±10V
0 to 10V
0 to ±10V
0 to to 5V
0 to ±5V
0 to 10V
0 to ±5V
0 to 5V
0 to ±10V
0 to 10V
0 to ±5V
0 to 5V
0 to ±10V
4 to 20mA
0 to ±5V
4 to 20mA
0 to ±10V
0 to 10V
0 to ±10V
0 to 5V
0 to ±5V
0 to 10V
0 to ±5V
0 to 5V
0 to ±10V
0 to 10V
0 to ±5V
0 to 5V
0 to ±10V
4 to 20mA
0 to ±5V
4 to 20mA
0 to ±10V
0 to ±10V
×
0 to ±5V
0 to ±5V
0 to 10V
×
0 to 5V
According to
0 to ±10V
Pr. 267 setting
×
0 to ±5V
0: 4 to 20mA
0 to ±10V
(initial value)
0 to ±10V
1: 0 to 5V
×
2: 0 to 10V
0 to ±5V
0 to ±5V
0 to 10V
×
0 to 5V
0 to ±10V
×
0 to ±5V
Frequency setting by analog input (terminal 1, 2, 4)
Pr.73, Pr.267
Pr.73, Pr.242, Pr.243,
Pr.252, Pr.253
Pr.74
Pr.125, Pr.126, Pr.241,
C2 to C7 (Pr.902 to
Pr.905)
Setting Range
Select the input specifications of the
0 to 7, 10 to 17
terminals 1, 2.
0
Terminal 4 input 4 to 20mA
1
Terminal 4 input 0 to 5V
2
Terminal 4 input 0 to 10V
indicates the main speed setting)
Compensation Input Terminal
and Compensation Method
Terminal 1
Added compensation
Terminal 2
Override
×
Terminal 1
Added compensation
Terminal 2
Override
Terminal 1
Added compensation
Terminal 1
Added compensation
Terminal 2
Override
Terminal 1
Added compensation
Terminal 2
Override
Terminal 1
Added compensation
Refer to page
125
127
128
129
Pr. 72
page 124
Pr.74
Description
page 128
Pr.266
page 112
Pr.268
page 100
Polarity
Reversible
No
Yes
No*
Yes
125
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents