GE B30 Instruction Manual page 456

Bus differential system, ur series
Hide thumbs Also See for B30:
Table of Contents

Advertisement

B.4 MEMORY MAPPING
F119
ENUMERATION: FLEXCURVE™ PICKUP RATIOS
mask
value
mask
0
0.00
30
1
0.05
31
B
2
0.10
32
3
0.15
33
4
0.20
34
5
0.25
35
6
0.30
36
7
0.35
37
8
0.40
38
9
0.45
39
10
0.48
40
11
0.50
41
12
0.52
42
13
0.54
43
14
0.56
44
15
0.58
45
16
0.60
46
17
0.62
47
18
0.64
48
19
0.66
49
20
0.68
50
21
0.70
51
22
0.72
52
23
0.74
53
24
0.76
54
25
0.78
55
26
0.80
56
27
0.82
57
28
0.84
58
29
0.86
59
F122
ENUMERATION: ELEMENT INPUT SIGNAL TYPE
0 = Phasor, 1 = RMS
F123
ENUMERATION: CT SECONDARY
0 = 1 A, 1 = 5 A
F124
ENUMERATION: LIST OF ELEMENTS
bitmask
element
16
Phase Time Overcurrent 1
17
Phase Time Overcurrent 2
24
Phase Directional Overcurrent 1
25
Phase Directional Overcurrent 2
32
Neutral Instantaneous Overcurrent 1
B-62
value
mask
value
mask
0.88
60
2.90
90
0.90
61
3.00
91
0.91
62
3.10
92
0.92
63
3.20
93
0.93
64
3.30
94
0.94
65
3.40
95
0.95
66
3.50
96
0.96
67
3.60
97
0.97
68
3.70
98
0.98
69
3.80
99
1.03
70
3.90
100
1.05
71
4.00
101
1.10
72
4.10
102
1.20
73
4.20
103
1.30
74
4.30
104
1.40
75
4.40
105
1.50
76
4.50
106
1.60
77
4.60
107
1.70
78
4.70
108
1.80
79
4.80
109
1.90
80
4.90
110
2.00
81
5.00
111
2.10
82
5.10
112
2.20
83
5.20
113
2.30
84
5.30
114
2.40
85
5.40
115
2.50
86
5.50
116
2.60
87
5.60
117
2.70
88
5.70
118
2.80
89
5.80
119
B30 Bus Differential System
bitmask
element
33
Neutral Instantaneous Overcurrent 2
34
Neutral Instantaneous Overcurrent 3
35
Neutral Instantaneous Overcurrent 4
value
36
Neutral Instantaneous Overcurrent 5
5.90
37
Neutral Instantaneous Overcurrent 6
6.00
48
Neutral Time Overcurrent 1
6.50
49
Neutral Time Overcurrent 2
7.00
50
Neutral Time Overcurrent 3
7.50
51
Neutral Time Overcurrent 4
8.00
64
Ground Instantaneous Overcurrent 1
8.50
65
Ground Instantaneous Overcurrent 2
9.00
66
Ground Instantaneous Overcurrent 3
9.50
67
Ground Instantaneous Overcurrent 4
10.00
68
Ground Instantaneous Overcurrent 5
10.50
69
Ground Instantaneous Overcurrent 6
11.00
80
Ground Time Overcurrent 1
11.50
81
Ground Time Overcurrent 2
12.00
82
Ground Time Overcurrent 3
12.50
83
Ground Time Overcurrent 4
13.00
84
Ground Time Overcurrent 5
13.50
85
Ground Time Overcurrent 6
14.00
101
Opposite Phase Rotation
14.50
133
Bus Zone 1
15.00
134
Bus Zone 2
15.50
144
Phase Undervoltage 1
16.00
145
Phase Undervoltage 2
16.50
146
Phase Undervoltage 3
17.00
148
Auxiliary Overvoltage 1
17.50
150
Auxiliary Overvoltage 3
18.00
156
Neutral Overvoltage 1
18.50
251
CT Trouble 1
19.00
252
CT Trouble 2
19.50
280
Breaker Failure 1
20.00
281
Breaker Failure 2
282
Breaker Failure 3
283
Breaker Failure 4
284
Breaker Failure 5
285
Breaker Failure 6
336
Setting Group
337
Reset
388
Selector 1
389
Selector 2
390
Control pushbutton 1
391
Control pushbutton 2
392
Control pushbutton 3
393
Control pushbutton 4
394
Control pushbutton 5
395
Control pushbutton 6
396
Control pushbutton 7
400
FlexElement™ 1
401
FlexElement™ 2
402
FlexElement™ 3
403
FlexElement™ 4
APPENDIX B
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents